Commissioning, Parameter Setup
•
Before starting make sure that all gaskets and seals and screwed connections are installed correctly.
•
Set the desired parameters.
•
Set parameters can be reviewed in the individual menu items.
•
Most important parameters can be reviewed on the status-display quickly.
•
Parameters can be set during operation.
•
Please note that a change in the parameters during operation can affect the reliability of the system!
Parameters
Description
Values
Factory Defaults
SP1 / FH1
set point 1 or
upper window value 1
OFF; >= 0,5% FS up to 100% FS
75% FS
RP1 / FL1
(1)
re-set point 1 or
lower window value 1
0% FS up to SP -0,5% FS (+0,5% FS if SP < 0)
74,5% FS
SP2 / FH2
(2)
set point 2 or
upper window value 2
OFF; >= 0,5% FS up to 100% FS
25% FS
RP2 / FL2
(1,2)
re-set point 2 or
lower window value 2
0% FS up to SP -0,5% FS (+0,5% FS if SP < 0)
24,5% FS
DS1
switch delay 1
OFF; 0,2 up to 50 s
OFF
DR1
re-set switch delay 1
OFF; 0,2 up to 50 s
OFF
DS2
(2)
switch delay 2
OFF; 0,2 up to 50 s
OFF
DR2
(2)
re-set switch delay 2
OFF; 0,2 up to 50 s
OFF
OU1
switching function 1
HNO (hystersis function, normally open)
HNC (hystersis function, normally closed)
FNO (hystersis function, normally open)
FNC (hystersis function, normally closed)
HNO
OU2
(2)
switching function 2
HNO (hystersis function, normally open)
HNC (hystersis function, normally closed)
FNO (hystersis function, normally open)
FNC (hystersis function, normally closed)
HNO
OUA
(3)
configuration
analogue output
I (4 - 20 mA = 0 - 100% FS)
I INV (4 - 20 mA = 100 - 0% FS)
I
UNI
pressure unit
bar; mbar; MPa; kPa; psi; %
bar
DISP
autom. display shut-off
OFF; 1 - 60 min
OFF
DISR
display rotation
NO (standard display)
YES (display rotated by 180°)
NO
ZERO
zero correction
NO; 1% FS
(4)
NO
PASS
password protection
NO; 0000 - 9999
NO
LANG
language for text menu
DE; EN; ES; FR; IT; OFF
DE
(1)
menu item not available, when corresponding output is turned OFF
(2)
only 2P
(3)
only 1PA
(4)
for pressure ranges < 4 bar max zero corr/- 50 mbar
Parameters, Description, Values, Factory Defaults