![Pintek PW-3063R Instruction Manual Download Page 13](http://html.mh-extra.com/html/pintek/pw-3063r/pw-3063r_instruction-manual_1557770013.webp)
10
DC POWER SUPPLY
WARNING
The maximum output voltage of the system is never exceeds 240V.
5. Parallel Mode:
The power supply 4063R can be connected two or more units in parallel to obtain a
higher current output (Max. 24A only).
5-1. Set all the 4063R which will be connected in parallel operation under parallel
tracking mode as described on section 3, parallel tracking mode and adjust all units to
the same output voltage
5-2. Parallel connected the "+" master output of all unit and “
-
" slave output of all
units in the system.
5-3. The output voltage of the system is the same as the units been set. The output
current of the system is the sum of each unit.
WARNING
The Max. output current of the system never exceeds 24A.
6. Fixed 5V/3A output:
This is the standard 5V/3A-power output for use of TTL logic circuit. When the load
exceed 3A, the red overload LED will light up. The output voltage will lower and the
power supply will be under C.C. mode.
4-1. Set all the 4063R which would be connected in serial operation under serial
tracking mode as described on section 2.
4-2. Connect the "
-
" slave output terminal of the unit 1 to the "+" master output
terminal of the unit 2.
4-3. The output voltage terminals will be the "+" master output terminal of the unit 1
and the "
-
" slave output terminal of the unit 2.
4-4. If the connected units are more than 2. Connect the "+" master output terminal of
the 3rd unit to the "
-
" slave output terminal of the unit 2. etc. The output voltage of
st
the system will be the "+" master output terminal of the 1 unit to the "
-
" slave output
terminal of the last unit.