background image

CONSUMER: READ AND SAVE THESE INSTRUCTIONS

GENERAL HAZARD WARNING:

READ AND UNDERSTAND ALL OF THE INSTRUCTIONS 

IN THIS MANUAL BEFORE ASSEMBLING, STARTING, OR 

SERVICING THE HEATER. 

Be sure to comply with the instructions and warnings provided 

with this heater. Failure to comply can result in fire or explosion that can cause property loss, 

bodily injury, or loss of life. Only persons who can follow and understand these instructions 

should operate or service this heater. If you need heater info; such as an operating manual, 

labels, etcetera, contact Pinnacle Climate Technologies at 866-676-1989.

NOT FOR USE IN RESIDENTIAL LIVING 

AREAS OR IN ENCLOSED SPACES 

WITHOUT ADEQUATE VENTILATION. 

FOR OUTDOOR USE. INDOOR USE 

PERMITTED ONLY FOR: THE TEMPORARY HEATING OF 

ADEQUATELY VENTILATED BUILDINGS OR STRUCTURES UNDER 

CONSTRUCTION, ALTERATION OR REPAIR. 

This is an unvented 

portable heater that uses air (Oxygen) from within the area in which 

it is used.  Failure to provide adequate combustion and ventilation air 

will result in asphyxiation, carbon monoxide poisoning, bodily injury or 

death. Refer to “Ventilation” on Page 7.

MODEL NUMBERS:

REM-80-OFR-O / REM-125-OFR-O

Factory ID: 001

DANGER

DANGER

User’s Manual & 

Operating Instructions

KEROSENE RADIANT HEATER

1 Industrial Blvd #101, Sauk Rapids, MN 56379 USA • Toll Free 

(866) 676-1989

Fax: 320-251-2922 • Web: 

www.remingtonheater.com

 • Email: [email protected]

© 2018 Pinnacle Climate Technologies, Inc.

RGR

F-403

U.S. Patent No. 9,644,863

Locating Your Serial Number:

Your serial number can be found on a blue label on the left side cover. It will begin with the letter 

“S” followed by 9 digits. For Example: S160901126. Have your Serial Number ready before calling 

customer service at 866-676-1989.

Summary of Contents for Remington REM-125-OFR-O

Page 1: ...QUATELY VENTILATED BUILDINGS OR STRUCTURES UNDER CONSTRUCTION ALTERATION OR REPAIR This is an unvented portable heater that uses air Oxygen from within the area in which it is used Failure to provide...

Page 2: ...ATER WHEN THE CHAMBER IS HOT WARNING WARNING WARNING FIRE BURN INHALATION AND EXPLOSION HAZARD Keep combustibles such as building materials paper or cardboard a safe distance away from the heater as r...

Page 3: ...The products described in this manual are kerosene direct fired forced air heaters Kerosene forced air heaters are primarily intended for use for temporary heating of buildings under construction alte...

Page 4: ...ption Gal Hr L Hr 0 63 2 38 0 85 3 22 Fuel Tank Capacity Gal L 4 15 14 14 53 00 Max Operating Hours 6 20 Volts AC Hz 120V 60Hz 120V 60Hz Amps 3 15 3 15 Heating Area ft 2 2000 3125 Specifications subje...

Page 5: ...Attach the handle while still in the box for easier unpacking see Figures 1 and 2 Carry Handle 1 Black Screws 2 80 OFR O 1 Remove existing screws from shell ring on either side of heater see Figure 3...

Page 6: ...ed see Figure 8 4 Attach Radiant Visors to the top and bottom rear of the Radiant Cone Assembly using extra screws included 5 Attach top safety guard using the two outer most extra screws on the top o...

Page 7: ...ct sunlight or near a source of heat NEVER use Kerosene that has been stored from one season to the next Kerosene deteriorates over time OLD Kerosene WILL NOT BURN PROPERLY IN THIS HEATER NOTE Kerosen...

Page 8: ...fails to ignite check this fuse first and replace if necessary Also check the power source to be sure the proper voltage is being provided to the heater 1 Complete steps 1 3 above 2 Push the power swi...

Page 9: ...SPARK PLUG Clean and re gap every 600 hours of operation or replace as needed After removing the Spark Plug clean the terminals with a wire brush Re gap the terminals to 0 140 3 5 mm see Figure 12 FAN...

Page 10: ...ozzle in clean Kerosene or diesel to help loosen any particles see Figure 14a and 14b PHOTOCELL The photocell should be cleaned at least once per heating season or more depending on conditions Use a c...

Page 11: ...te Technologies Inc Kerosene Radiant Heater User s Manual NEVER LEAVE HEATER UNATTENDED WHILE BURNING OR WHILE CONNECTED TO A POWER SOURCE 11 125 OFR O WIRING DIAGRAMS AC 120V 60Hz AC 250V 3 15A ELECT...

Page 12: ...lug 3 Clean replace Fuel Filter 4 Clean replace Nozzle 5 Rinse out fuel tank with clean fresh Kerosene diesel 6 Inspect all electrical connections See Wiring Diagrams Page 11 7 Re attach Transformer w...

Page 13: ...s Inc Kerosene Radiant Heater User s Manual NEVER LEAVE HEATER UNATTENDED WHILE BURNING OR WHILE CONNECTED TO A POWER SOURCE 13 EXPLODED VIEW 25 23 24 9 21 22 20 19 26 10 7 28 6 4 3 1 2 27 8 12 13 29...

Page 14: ...0650 9 Ignitor 75 025 0120 10 Main PCB Assembly 75 025 0400 11 Tip Over Sensor 75 051 0200 12 Cooling Motor Assembly 75 047 0250 13 Cooling Fan 75 047 0200 14 Handle 75 001 0060 15 Temperature Limit...

Page 15: ...erosene Radiant Heater User s Manual NEVER LEAVE HEATER UNATTENDED WHILE BURNING OR WHILE CONNECTED TO A POWER SOURCE 15 1 2 4 3 5 6 7 8 9 10 11 12 13 14 15 16 17 18 24 20 22 21 30 23 26 19 34 27 29 4...

Page 16: ...ump 72 027 0100 11 Main PCB and Fuse 72 025 0450 12 Tip Over Sensor 75 051 0200 13 Power Cord 72 032 0150 14 Power Switch 72 012 0120 15 Back Cover 72 013 0110 16 Panel sub PCB 72 014 0100 17 Blower M...

Page 17: ...If Pinnacle Climate Technnologies Inc finds the item to be in normal operating condition or not defective the item will be returned freight collect This Limited Warranty is in lieu of all other expres...

Page 18: ...1 Industrial Blvd 101 Sauk Rapids MN 56379 USA Toll Free 866 676 1989 Fax 320 251 2922 Web www remingtonheater com Email info pinnacleclimate com 2018 Pinnacle Climate Technologies Inc...

Page 19: ...FICIOS ADECUADAMENTE VENTILADOS O ESTRUCTURAS EN CONSTRUCCI N MODIFICACI N O REPARACI N Este es un calentador port til sin ventilaci n que utiliza aire ox geno del rea en la que se usa Si no se sumini...

Page 20: ...ENCIA NO ENCIENDA EL CALENTADOR CUANDO LA C MARA EST CALIENTE ADVERTENCIA PELIGRO DE INCENDIO QUEMADURAS INHALACI N Y EXPLOSI N Mantenga los combustibles como materiales de construcci n papel o cart n...

Page 21: ...Los productos descritos en este manual son calentadores de aire forzado de fuego directo de queroseno Los calentadores de aire forzado de queroseno est n hechos expresamente para calefacci n temporal...

Page 22: ...z 120 V 60 Hz Amperaje 3 15 3 15 rea de calefacci n pies2 m 2 2000 185 3125 290 Las especificaciones pueden cambiar sin previo aviso CARACTER STICAS PROTECCI N DE SEGURIDAD PLACA DE CALOR ANILLO DE LA...

Page 23: ...cuando a n est en la caja para facilitar el desempaque vea las Figuras 1 y 2 Asa 1 Tornillos negros 2 80 OFR O 1 Retire los tornillos existentes del anillo de la coraza en ambos lados del calentador...

Page 24: ...8 4 Sujete los visores radiantes a la parte trasera superior e inferior del conjunto del cono radiante con los tornillos adicionales incluidos 5 Sujete la protecci n de seguridad superior con los dos...

Page 25: ...e queroseno que se haya estado almacenado de una temporada a la siguiente El queroseno se deteriora con el tiempo EL queroseno VIEJO NO SE QUEMAR ADECUADAMENTE EN ESTE CALENTADOR NOTA El queroseno deb...

Page 26: ...este fusible y reempl celo si es necesario Tambi n revise la fuente de alimentaci n el ctrica para asegurarse que se est suministrando el voltaje correcto al calentador 1 Complete los pasos 1 a 3 desc...

Page 27: ...trodos de la buj a despu s de cada 600 horas de funcionamiento o reempl cela seg n sea necesario Despu s de extraer la buj a limpie las terminales con una cepillo de alambre Reajuste la separaci n de...

Page 28: ...jen las part culas vea las Figuras 14a y 14b FOTOC LULA La fotoc lula debe limpiarse al menos una vez por cada temporada de calefacci n o m s seg n las condiciones en que est Utilice un hisopo de algo...

Page 29: ...A BUJ A ENCENDEDOR MOTOR DE ENFRIAMIENTO PLACA DE CIRCUITOS IMPRESOS LUZ DE FUNCIONAMIENTO LUZ DE REVISI N DE ERROR PCI DE CONTROL INTERRUPTOR ANTIVUELCO INTERRUPTOR DE LIMITE DE TEMPERATURA FOTOC LUL...

Page 30: ...del tanque con queroseno o di sel nuevo y limpio 6 Inspeccione todas las conexiones el ctricas Consulte los Diagramas el ctricos en la p gina 11 7 Reconecte los cables del transformador a la buj a 8 R...

Page 31: ...l calentador radiante de queroseno NUNCA DEJE DESATENDIDO EL CALENTADOR MIENTRAS EST ENCENDIDO O MIENTRAS EST CONECTADO A UNA FUENTE DE ALIMENTACI N 13 VISTA DETALLADA 25 23 24 9 21 22 20 19 26 10 7 2...

Page 32: ...ctrica 75 027 0650 9 Encendedor 75 025 0120 10 Conjunto de la placa de circuitos impresos principal 75 025 0400 11 Interruptor antivuelco 75 051 0200 12 Conjunto del motor de enfriamiento 75 047 0250...

Page 33: ...ntador radiante de queroseno NUNCA DEJE DESATENDIDO EL CALENTADOR MIENTRAS EST ENCENDIDO O MIENTRAS EST CONECTADO A UNA FUENTE DE ALIMENTACI N 15 1 2 4 3 5 6 7 8 9 10 11 12 13 14 15 16 17 18 24 20 22...

Page 34: ...e 72 027 0100 11 Placa de circuitos impresos principal y fusible 72 025 0450 12 Interruptor antivuelco 75 051 0200 13 Cable el ctrico 72 032 0150 14 Interruptor de encendido 72 012 0120 15 Cubierta po...

Page 35: ...echnologies Inc descubre que el art culo est en condiciones normales de funcionamiento o que no est defectuoso se devolver el art culo con el flete por cobrar Esta Garant a Limitada reemplaza a todas...

Page 36: ...strial Blvd 101 Sauk Rapids MN 56379 USA Llamada sin costo 866 676 1989 Fax 320 251 2922 Sitio web www remingtonheater com Correo electr nico info pinnacleclimate com 2018 Pinnacle Climate Technologie...

Reviews: