Wiring
Operating Manual PSSu K S 16DO 0.5
22059-EN-08
20
6
Wiring
6.1
General wiring guidelines
Please note:
}
The actuators may be connected using unshielded cables.
}
The outputs do not need suppression for inductive loads.
}
Use copper wiring.
6.1.1
Connectors' mechanical connection
Please note:
}
The conductor cross section on the spring-loaded terminals without ferrules is 0,20 -
1,00 mm², 22 - 18 AWG.
}
If you are using multi-core or fine-core cables we recommend ferrules in accordance
with DIN 46228/Part 1 or DIN 46228/Part 4, 0.2 ... 1 mm
2
. To crimp the ferrules we re-
commend crimping pliers (crimp form A) conforming to EN 60947-1, such as the PZ 6/5
from Weidmüller, for example.
}
Terminal points per connection: 1
}
Stripping length: 8,0 mm
6.1.2
Connect/disconnect the cables
We recommend you use a screw driver with a 0.4 x 2.5 mm (DIN 5264) blade!
Strip the cable:
}
Strip the cable [1] and apply a ferrule if necessary (DIN 46228/Part 1 or DIN 46228/Part
4).
Connect cable:
}
Using the screwdriver, press the actuator button on the spring-loaded terminal down as
far as it will go [2], keep it held down and insert the stripped cable into the plug connec-
tion as far as it will go [2].
}
Check that the cable is firmly seated [3].
Disconnect cable:
}
Using the screwdriver, press the actuator button down as far as it will go [4], keep it
held down and pull the cable out of the plug connection [4].