PSEN op2H-SL Series
Operating Manual PSEN op2H-SL Series
1004304-EN-01
13
OSSD
EDM
2
t
1
t
On
Off
24 V
0 V
Fig.: Timing diagram for EDM
Legend
t
1
After the OSSD outputs are switched on, the EDM circuit must open within 350 ms
t
2
After the OSSD outputs are switched off, the EDM circuit must close within 100 ms
Use control elements whose dynamics match the times stated at t
1
and t
2
.
The function is activated or deactivated with the
Wiring [
30]
.
Cascading
During cascading, the safety outputs of a safety light grid are connected to an evaluation
device. A second safety light grid can be connected to this first safety light grid. The first
safety light grid is the master unit; the safety light grid connected to the master unit is the
slave unit.
}
Max. 2 slave units to one master unit
}
Max. overall length: 3600 mm
}
The master unit collects the results from the slave units and ensures synchronisation
between them, so that mutual interference is avoided
}
Each transmitter/receiver in the PSEN op2H-SL Series can be used both as a master
unit and a slave unit
}
Up to three areas can be monitored when two safety outputs are connected
Project configuration
Maintaining the safety distance
The minimum distance between the safety light grid and the hazardous machine compon-
ent should be such that the operator cannot reach the hazardous area until the hazardous
machine part has come to a standstill.