Operating Manual PSEN op2.1 L/ 2.2 TMuting Set
1003535EN01
13
}
Violate the protected field and check that
–
the OSSDs are switched off,
–
the red LED lights
–
the monitored machine is shut down.
}
Check that the safety light grid's response time and the machine's stopping perform
ance meet the specifications stated in the operating manual of the relevant safety light
grid.
}
Check that muting operates correctly. Access the protected field covered by the muting
sensors.
–
The muting lamp on the safety light grid must light.
–
The red LEDs on the muting sensors must light.
–
The OSSDs must be switched off.
–
The monitored machine must be shut down.
Set muting timeout
Time monitoring for the muting function can be set to
}
10 minutes or
}
to ∞
gestellt werden.
When the unit is delivered, this is already preset to 10 minutes.
CAUTION!
If time monitoring for the muting function is set to ∞, the muting function is
not cancelled until the muting sensors are no longer active.
This setting does not comply with the specifications of EN ISO 614961.
Avoid a situation in which permanent muting (on account of simultan
eous errors or constantly interrupted muting sensors) will not be de
tected.
Procedure for setting to ∞
Set DIP switches 1 and 5 to OFF.