PSEN cs5.13 M12/8 EX
Operating Manual PSEN cs5.13 M12/8 EX
22218-EN-04
| 17
INFORMATION
Only use safety relays with a 24 VDC supply voltage. Safety relays with a
wide-range power supply or in AC device versions have internal potential
isolation and are not suitable as evaluation devices.
}
The supply voltage to the safety switch must be protected with a 2 A to 4 A quick-acting
fuse.
}
Ensure the wiring and EMC requirements of EN 60204-1 are met.
}
When connecting in series, consider the requirements of manipulation protection and the
protection against bypassing or from overriding the safety switch (EN ISO 14119).
}
When the safety inputs of the safety switch are controlled by an upstream device, and
they are not wired with 24 V,
– They must be monitored for shorts across the contacts in dependence of the Perform-
ance Level or SIL level to be achieved
or
– The the faults at the safety inputs that can occur by shorts across contact will have to
be excluded by suitable measures (e.g. wiring in accordance with EN 602041).
}
Refer to the notes on wiring in EN 60079-14.
}
Any metallic parts (also accessories) must be connected to the equipotential bonding in
case of a risk of charging.
}
Ensure that the connector of the safety switch in the EX area is not removed or inserted.
Pin assignment, connector and cable
8-pin M12 connector
PIN
Connection
designation
Function
Wire colour
1
S21
Input, channel 2
white
2
A1
+24 VUB
brown
3
12
Output, channel1
green
4
22
Output, channel2
yellow
5
Y32
Signal output/diagnostic output
grey
6
S11
Input, channel 1
pink
7
A2
0 V UB
blue
8
Y1
Diagnostics input
red