Inputs
774738
774739
Max. overall cable resistance Rl-
max
Single-channel at UB AC
150 Ohm
150 Ohm
Dual-channel without detection
of shorts across contacts at UB
AC
150 Ohm
150 Ohm
Dual-channel with detection of
shorts across contacts at UB AC
100 Ohm
100 Ohm
Relay outputs
774738
774739
Number of output contacts
Safety contacts (N/O), instant-
aneous
3
3
Auxiliary contacts (N/C)
1
1
Max. short circuit current IK
1 kA
1 kA
Utilisation category
In accordance with the standard
EN 60947-4-1
EN 60947-4-1
Utilisation category of safety con-
tacts
AC1 at
240 V
240 V
Min. current
0,01 A
0,01 A
Max. current
8 A
8 A
Max. power
2000 VA
2000 VA
DC1 at
24 V
24 V
Min. current
0,01 A
0,01 A
Max. current
8 A
8 A
Max. power
200 W
200 W
Utilisation category of auxiliary con-
tacts
AC1 at
240 V
240 V
Min. current
0,01 A
0,01 A
Max. current
8 A
8 A
Max. power
2000 VA
2000 VA
DC1 at
24 V
24 V
Min. current
0,01 A
0,01 A
Max. current
8 A
8 A
Max. power
200 W
200 W
Utilisation category
In accordance with the standard
EN 60947-5-1
EN 60947-5-1
Utilisation category of safety con-
tacts
AC15 at
230 V
230 V
Max. current
5 A
5 A
DC13 (6 cycles/min) at
24 V
24 V
Max. current
7 A
7 A