Technical Details
Operating Manual PNOZ mc5.1p
21248-EN-03
19
8
Technical Details
General
Approvals
CCC, CE, EAC (Eurasian), KCC, KOSHA, TÜV, cU-
Lus Listed
Electrical data
Supply voltage
for
Module supply
internal
Via base unit
Voltage
5,0 V
Kind
DC
Voltage tolerance
-2 %/+2 %
Power consumption
2,0 W
Status indicator
LED
Fieldbus interface
Fieldbus interface
INTERBUS LWL
Device type
Slave
Transmission rates
2 MBit/s, 500 kBit/s
Connection
F-SMA connector
Times
Supply interruption before de-energisation
20 ms
Environmental data
Ambient temperature
In accordance with the standard
EN 60068-2-14
Temperature range
0 - 55 °C
Storage temperature
In accordance with the standard
EN 60068-2-1/-2
Temperature range
-25 - 70 °C
Climatic suitability
In accordance with the standard
EN 60068-2-30, EN 60068-2-78
Humidity
93 % r. h. at 40 °C
Condensation during operation
Not permitted
EMC
EN 61131-2
Vibration
In accordance with the standard
EN 60068-2-6
Frequency
10,0 - 150,0 Hz
Acceleration
1g
Shock stress
In accordance with the standard
EN 60068-2-27
Acceleration
15g
Duration
11 ms
Max. operating height above sea level
2000 m
Airgap creepage
In accordance with the standard
EN 61131-2
Overvoltage category
III
Pollution degree
2