Function description
Operating Manual PNOZ mc5.1p
21248-EN-03
11
4
Function description
4.1
Functions
The data to be transferred via INTERBUS LWL is selected and configured in the
PNOZmulti Configurator. The base unit and PNOZ fieldbus module PNOZ mc5.1p are con-
nected via a jumper. The fieldbus module is also supplied with voltage PNOZ mc5.1p via
this jumper. After the supply voltage is switched on or the safety system PNOZmulti is re-
set, the fieldbus module PNOZ mc5.1p is configured and started automatically.
4.2
Input and output data
The data is structured as follows:
}
Input area
The inputs are defined in the master and transferred to the PNOZmulti. Each input has
a number, e.g. input bit 4 of byte 1 has the number i12.
}
Output range
The outputs are defined in the PNOZmulti Configurator. Each output that is used is
given a number there, e.g. o0, o5... The status of output o0 is stored in bit 0 of byte 0;
the status of output o5 is stored in bit 5 of byte 0 etc.
}
Output range only: Byte 3
Bits 0 … 4: Status of LEDs on the PNOZmulti
–
Bit 0: OFAULT
–
Bit 1: IFAULT
–
Bit 2: FAULT
–
Bit 3: DIAG
–
Bit 4: RUN
Bit 5: Data is being exchanged.
Detailed information on data exchange (tables, segments) is available in the document
"Communication Interfaces" in the section entitled "Fieldbus modules".
4.3
Assigning the inputs/outputs in the PNOZmulti Configurator
to the INTERBUS inputs/outputs
Virtual inputs on PNOZmulti Configurator
i0 ... I7
i8 ... i15
i16 ... i23
Input data INTERBUS LWL
Byte 0: Bits 0 … 7
Byte 1: Bits 0 … 7
Byte 2: Bits 0 … 7
Virtual outputs on PNOZmulti Configurator o0 ... o7
o8 ... o15
o16 ... o23
Output data INTERBUS LWL
Byte 0: Bits 0 … 7
Byte 1: Bits 0 … 7
Byte 2: Bits 0 … 7
The number of virtual inputs and outputs can be extended to 128 (see document "Commu-
nication Interfaces" in the section entitled "Fieldbus modules")