PNOZ mc5.1p
Operating Manual 21248-EN-03
}
Configurable safety systems PNOZmulti
Page 1: ...PNOZ mc5 1p Operating Manual 21248 EN 03 Configurable safety systems PNOZmulti ...
Page 2: ...cumentation will be gratefully received Source code from third party manufacturers or open source software has been used for some components The relevant licence information is available on the Internet on the Pilz homepage Pilz PIT PMI PNOZ Primo PSEN PSS PVIS SafetyBUS p SafetyEYE SafetyNET p the spirit of safety are registered and protected trademarks of Pilz GmbH Co KG in some countries SD mea...
Page 3: ...ion 11 4 1 Functions 11 4 2 Input and output data 11 4 3 Assigning the inputs outputs in the PNOZmulti Configurator to the INTER BUS inputs outputs 11 4 4 Block diagram 12 Section 5 Installation 13 5 1 General installation guidelines 13 5 2 Dimensions in mm 13 5 3 Connecting the base unit and expansion modules 14 Section 6 Commissioning 15 6 1 Preparing for commissioning 15 6 2 Preparing for opera...
Page 4: ...Contents Operating Manual PNOZ mc5 1p 21248 EN 03 4 Section 9 Order reference 21 9 1 Product 21 9 2 Accessories 21 ...
Page 5: ... is particularly important is identified as follows DANGER This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive measures that can be taken WARNING This warning must be heeded It warns of a hazardous situation that could lead to serious injury and death and indicates preventive measures that can be taken CA...
Page 6: ...Introduction Operating Manual PNOZ mc5 1p 21248 EN 03 6 INFORMATION This gives advice on applications and provides information on special fea tures ...
Page 7: ... the PNOZmulti Configurator Connection for INTERBUS with fibre optic cable Transmission rate selectable between 500 kBit s and 2 MBit s Status indicators for communication with INTERBUS and for errors F SMA connection technology Max 1 PNOZ mc5 1p can be connected to the base unit In the PNOZmulti Configurator 24 inputs standard and 24 outputs standard can be configured for communication via a fiel...
Page 8: ...Overview Operating Manual PNOZ mc5 1p 21248 EN 03 8 2 3 Front view Legend IBS IN Remote bus IN TX Transmitter RX Receiver IBS OUT Remote bus OUT TX Transmitter RX Receiver LEDs CR CC BA RD TR FO1 FO2 ...
Page 9: ...t can be connected The configurable small control systems PNOZmulti are used for the safety related interrup tion of safety circuits and are designed for use in E STOP equipment Safety circuits in accordance with VDE 0113 Part 1 and EN 60204 1 The expansion module may not be used for safety related functions The following is deemed improper use in particular Any component technical or electrical m...
Page 10: ...nd liability All claims to warranty and liability will be rendered invalid if The product was used contrary to the purpose for which it is intended Damage can be attributed to not having followed the guidelines in the manual Operating personnel are not suitably qualified Any type of modification has been made e g exchanging components on the PCB boards soldering work etc 3 3 3 Disposal When decomm...
Page 11: ...rator Each output that is used is given a number there e g o0 o5 The status of output o0 is stored in bit 0 of byte 0 the status of output o5 is stored in bit 5 of byte 0 etc Output range only Byte 3 Bits 0 4 Status of LEDs on the PNOZmulti Bit 0 OFAULT Bit 1 IFAULT Bit 2 FAULT Bit 3 DIAG Bit 4 RUN Bit 5 Data is being exchanged Detailed information on data exchange tables segments is available in ...
Page 12: ...Function description Operating Manual PNOZ mc5 1p 21248 EN 03 12 4 4 Block diagram Base unit IBS OUT TX RX RX IBS IN TX ...
Page 13: ...ng rail in an upright position so that the earthing springs on the control system are pressed on to the mounting rail The ambient temperature of the PNOZmulti units in the control cabinet must not exceed the figure stated in the technical details otherwise air conditioning will be required To comply with EMC requirements the mounting rail must have a low impedance con nection to the control cabine...
Page 14: ...base unit and the expansion module as described in the operating instructions for the base units Do not connect a terminator to the last expansion module on the left hand side Install the expansion module in the position in which it is configured in the PNOZmulti Configurator A distance of at least 20 mm must be maintained between the fieldbus module PNOZ mc5 1p and any external heat sources ...
Page 15: ...riods of direct eye contact with the LED Use only the following fibre optic cables Polymer fibre fibre type 980 1000 µm HCS fibre fibre type 200 230 µm NOTICE When installing please refer to the Installation Manual for fibre optic cables issued by the INTERBUS User Organisation 6 2 Preparing for operation Connect fibre optic cable Connect the FO cable to the F SMA plug in connector on the transmit...
Page 16: ...eatures RX and TX F SMA screw connections for IBS IN and RX and TX for IBS OUT for connecting to the INTERBUS FO IBS IN Remote bus IN TX Transmitter RX Receiver IBS OUT Remote bus OUT TX Transmitter RX Receiver 6 4 Setting the transmission rate The transmission rate is set using a jumper You can choose between 500 kBit s and 2 MBit s 500 kBit s 500k 2M 2 MBit s 500k 2M 6 5 Connecting the supply vo...
Page 17: ...d as described in the operat ing instructions for the base unit NOTICE For the commissioning and after every program change you must check whether the safety devices are functioning correctly 6 7 Connection example The sender and receiver of the incoming and outgoing remote buses are configured in a crossover formation Cover unused connections with a protective cap PNOZ mc5 1p INTERBUS Master INTE...
Page 18: ...he cable connection is in order and the INTERBUS Master is not in a reset condition The cable connection is defective or the INTERBUS Master is in a reset condition OM green Data traffic present No data traffic RD yellow The remote bus is switched off remote bus disabled The remote bus is switched on remote bus enabled TR green PCP transmission is active Reaction period 500 ms PCP transmission is ...
Page 19: ... Environmental data Ambient temperature In accordance with the standard EN 60068 2 14 Temperature range 0 55 C Storage temperature In accordance with the standard EN 60068 2 1 2 Temperature range 25 70 C Climatic suitability In accordance with the standard EN 60068 2 30 EN 60068 2 78 Humidity 93 r h at 40 C Condensation during operation Not permitted EMC EN 61131 2 Vibration In accordance with the...
Page 20: ...Mounting area e g control cabinet IP54 Housing IP20 Terminals IP20 Mechanical data Mounting position Horizontal on top hat rail DIN rail Top hat rail 35 x 7 5 EN 50022 Recess width 27 mm Material Bottom PPO UL 94 V0 Front ABS UL 94 V0 Dimensions Height 94 0 mm Width 22 5 mm Depth 121 0 mm Weight 145 g Where standards are undated the 2007 05 latest editions shall apply ...
Page 21: ...ting Manual PNOZ mc5 1p 21248 EN 03 21 9 Order reference 9 1 Product Product type Features Order No PNOZ mc5 1p Fieldbus module INTERBUS FO 773 728 9 2 Accessories Jumper Product type Features Order No KOP XE Jumper 774 639 ...
Page 22: ...ET p the spirit of safety are registered and protected trademarks of Pilz GmbH Co KG in some countries We would point out that product features may vary from the details stated in this document depending on the status at the time of publication and the scope of the equipment We accept no responsibility for the validity accuracy and entirety of the text and graphics presented in this information Pl...