6.3
Preparing for operation
6
Commissioning
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
6-6
6.3.2.2
Load project via integrated interface
Load project via integrated interface
6-
Verdrahtung_multi_Basis_Betr_erstes_Mal_Schnittstelle_BA
Procedure:
`
Insert a chip card into the chip card slot on the base unit.
`
Connect the computer containing the PNOZmulti Configurator to the
base unit via the interface.
`
Switch on the supply voltage.
`
Download the project (see PNOZmulti Configurator's online help).
ETH_Info_PC_mit_Ethernet-Karte
6.3.3
Download modified project to the PNOZmulti safety system
Download modified project to the PNOZmulti safety system
6-
6.3.3.1
Load modified project from chip card
Load modified project from chip card
6-
Verdrahtung_multi_Basis_Betr_geaend_Projekt_von_Chipkarte_BA
To download data via chip card, the existing configuration data must
first be deleted (general reset of device).
Procedure:
`
Switch off the supply voltage.
`
Disconnect all the output terminals.
`
Jumper OA0-I19 on the base unit.
`
Switch on the supply voltage.
When the "DIAG" LED on the base unit flashes, the memory has been
cleared. The project data can now be downloaded:
`
Switch off the supply voltage.
`
Remove the old chip card from the chip card slot on the base unit.
`
Remove the link from OA0-I19 on the base unit.
`
Insert the chip card containing the current project into the card slot.
`
Switch on the supply voltage.
6.3.3.2
Load modified project via integrated interface
Load modified project via integrated interface
6-
Verdrahtung_multi_Basis_Betr_geaend_Projekt_Schnittstelle_BA
Proceed as described for the initial commissioning
INFORMATION
You will need a PC with an Ethernet card in order to establish an
Ethernet connection.