Technical details
Operating Manual PNOZ m EF 1MM
1003108-EN-11
| 47
Mechanical data
Mounting type
plug-in
Conductor cross section with screw terminals
1 core flexible
0,25 - 2,5 mm², 24 - 12 AWG
2 core with the same cross section, flexible without
crimp connectors or with TWIN crimp connectors
0,2 - 1,5 mm², 24 - 16 AWG
Torque setting with screw terminals
0,5 Nm
Conductor cross section with spring-loaded terminals:
Flexible with/without crimp connector
0,2 - 2,5 mm², 24 - 12 AWG
Spring-loaded terminals: Terminal points per connec-
tion
2
Stripping length with spring-loaded terminals
9 mm
Dimensions
Height
101,4 mm
Width
22,5 mm
Depth
111 mm
Weight
90 g
Where standards are undated, the 2018-09 latest editions shall apply.
8.1
Safety characteristic data
Operating
mode
EN ISO
13849-1:
2015
PL
EN ISO
13849-1:
2015
Category
EN IEC
62061
SIL CL
EN IEC
62061
PFH
D
[1/h]
IEC 61511
SIL
IEC 61511
PFD
EN ISO
13849-1:
2015
T
M
[year]
Monitoring 1
encoder
PL d
Cat. 2
SIL CL 2
1,80E-08
SIL 2
1,58E-03
20
Monitoring 2
encoder
PL e
Cat. 3
SIL CL 3
1,01E-09
SIL 3
8,41E-05
20
Monitoring
safe en-
coder
PL e
Cat. 4
SIL CL 3
2,35E-09
SIL 3
2,04E-04
20
Logic
PL e
Cat. 4
SIL CL 3
3,37E-10
SIL 3
2,88E-05
20
All the units used within a safety function must be considered when calculating the safety
characteristic data.
INFORMATION
A safety function's SIL/PL values are
not
identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use