Commissioning
Operating Manual PNOZ m EF 1MM
1003108-EN-11
| 33
6.3
Connection of proximity switches
The following proximity switch combinations can be connected:
}
A: pnp, B: pnp
}
A: npn, B: npn
}
A: pnp, B: npn
}
A: npn, B: pnp
When connecting proximity switches please note:
}
Proximity switches can be connected to
– terminals A12, B12, GND for axis 1
or
– tracks A, B and GND of the Mini-IO socket (X12 for axis 1).
}
Track S (S12) should be used to monitor the supply voltage (see drawing). A permitted
voltage range can be entered in the menu.
}
Connect the proximity switch to 24 VDC of the power supply.
}
When connecting the proximity switches, please refer to the chapter entitled "EMC-com-
pliant wiring".
}
Invalid signals may occur with long cable lengths. In this case we recommend that you
connect a resistor between the signal lines, as shown in the diagrams.
}
Connection of the proximity switches may only be performed in three-wire technology and
not in two-wire technology.
}
Special features for proximity switches with reduced diagnostics:
– A: pnp, B: pnp
– It is permitted that both proximity switches are energised simultaneously.
– The safety level is reduced.
– The cables for connecting the proximity switches must be laid separately.
– The supply voltage of the proximity switches must be monitored (e.g. via track S).
A12
B12
GND
S12