background image

Technical details

Operating Manual PIT m4SEU
1004648-EN-02

| 66

No.

Measures against CCF

Score

Confirmed by

1

Physical separation between signal paths, for example:

}

separation in wiring/piping;

}

detection of short circuits and open circuits in cables by dynamic
test;

}

separate shielding for the signal path of each channel;

}

sufficient clearances and creepage distances on printed-circuit
boards.

15

Pilz

3.1

Protection against over-voltage, over-pressure, over-current, over-
temperature, etc.

15

Customer

6.1

For electric/electronic systems, prevention of contamination and
electromagnetic disturbances (EMC) to protect against common
cause failures in accordance with appropriate standards (e.g. IEC
61326-3-1).
Fluidic systems: filtration of the pressure medium, prevention of
dirt intake, drainage of compressed air, e.g. in compliance with
the component manufacturers' requirements concerning purity of
the pressure medium.
NOTE: For combined fluidic and electric systems, both aspects
should be considered.

25

Pilz

6.2

Other influences:
Consideration of the requirements for immunity to all relevant en-
vironmental influences such as, temperature, shock, vibration, hu-
midity (e.g. as specified in relevant standards).

10

Customer

Total

65

Extract from Table F.1 (EN ISO 13849-1)

}

The user must provide the following data:

– The pushbutton must meet Cat. B

– To calculate the MTTF

D

 of the pushbutton:

- B

10d

 value

- n

op

 (average number of operations per year) of the pushbutton

INFORMATION

A safety function's SIL/PL values are 

not

 identical to the SIL/PL values of

the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.

Summary of Contents for PIT m4SEU

Page 1: ...PIT m4SEU Operating Manual 1004648 EN 02 Control and signal devices...

Page 2: ...nta tion will be gratefully received Source code from third party manufacturers or open source software has been used for some components The relevant licence information is available on the Internet...

Page 3: ...5 5 1 1 Operator actions 25 5 5 1 2 Device error 27 5 5 1 3 Application error No authorisation 27 5 5 1 4 Application error Pushbutton operated incorrectly 29 5 6 Key ID interface 31 5 6 1 Key ID numb...

Page 4: ...l mode service 57 8 3 Monitoring of operating time 58 8 4 Switchover time 58 8 5 Device status display 58 8 6 Troubleshooting 59 8 6 1 Delete error 59 8 7 Diagnostics 59 8 7 1 Status information about...

Page 5: ...particularly important is identified as follows DANGER This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventiv...

Page 6: ...Introduction Operating Manual PIT m4SEU 1004648 EN 02 6 INFORMATION This gives advice on applications and provides information on special fea tures...

Page 7: ...ccess for op erating mode selection Pushbutton for selecting the operating mode one pushbutton per operating mode Display elements for the operating mode one display element per operating mode Safety...

Page 8: ...ce for status information consisting of 4 signal outputs 24 V Status information is divided into information classes Operator actions Insert transponder key Remove transponder key Select operating mod...

Page 9: ...Supply voltage A1 A2 Interface for status information SIo0 SIo3 Key ID interface IDo0 IDo3 and IDi0 IDi1 X3 Inputs I1 I4 Outputs O1 O4 X4 PITreader interface 1 Device name and order number 2 Serial nu...

Page 10: ...verview Operating Manual PIT m4SEU 1004648 EN 02 10 4 Fig Side view Legend 4 DIP switch for configuring the switching behaviour and configuring the communica tion mode for downloading the Key ID numbe...

Page 11: ...in the most recently se lected operating mode depending on the device configuration see also Configuration of functions 19 The following access restriction requirements security functions for operati...

Page 12: ...nstalled in other environments If installed in other environments measures should be taken to comply with the applicable standards and directives for the respective installation site with regard to in...

Page 13: ...lowed the guidelines in the manual Operating personnel are not suitably qualified Any type of modification has been made e g exchanging components on the PCB boards soldering work etc 3 2 3 Disposal I...

Page 14: ...ld have at least 8 characters The password should contain upper and lower case characters as well as special characters and numbers If possible the password should not be available in dictionaries The...

Page 15: ...Security Operating Manual PIT m4SEU 1004648 EN 02 15 Company firewall Machine firewall Company network Machine network Internet Configuration computer Product Fig Example network topology...

Page 16: ...in period see Monitoring of operating time 58 Each input pushbutton is assigned a monitored semiconductor output see Operating mode interface 22 Operating the pushbutton switches the semiconductor out...

Page 17: ...TxD RxD Fig Block diagram Legend Transponder Key Transponder key to enable a change of operating mode PITreader Authentication system PITreader Interface 0V 24V TxD RxD Interface for connecting the P...

Page 18: ...sponder keys is available in the PITreader op erating manual INFORMATION Only the transponder key permissions 1 5 which are detected by the au thentication system PITreader enable operating mode selec...

Page 19: ...n mode 33 Advanced communication mode 34 NOTICE It is essential to note The configuration may only be performed by a competent person The configuration must be performed when the supply voltage is swi...

Page 20: ...fallback Transmitter or hand shake controlled com munication mode D4 4 3 2 1 Off On OM storage Transmitter or hand shake controlled com munication mode D5 4 3 2 1 Off On OM1 OM4 OM retention Advanced...

Page 21: ...lit OM1 has a 1 signal Service fall back OM5 must be act ive the operating mode switches to OM1 the display element 1 is lit OM1 has a 1 signal the operating mode OM1 is activ ated the display element...

Page 22: ...ailable for this purpose see Control elements 9 The individual switch settings and the resulting switching behaviour are described in the chapter entitled Configuration of functions 19 5 4 2 Control p...

Page 23: ...at time the selected operating mode is again displayed Status information Information class SIo3 MSB SIo2 SIo1 SIo0 LSB Value in Hex Operating mode preselection is switched 5 Response 0 0 0 0 0h Reser...

Page 24: ...ication error No authorisation 27 3 A Device error Dh is registered if the DIP switch setting is changed during operation see Delete error 59 or if one of the operating mode outputs MSO1 MSO5 is stuck...

Page 25: ...ng mode 1 Start position OM1 selected DIP switch in default setting 2 Operator action Insert transponder key on the PITreader e g permission 2 3 Operator action Select operating mode e g Press pushbut...

Page 26: ...5 s e l e c t e d T r a n s p o n d e r K e y r e m o v e d O M 1 s e l e c t e d O M 1 O M 4 s e l e c t e d T r a n s p o n d e r K e y r e m o v e d 8h 3h 8h Bh as before Fh Fh t t Key Mode 01 04 S...

Page 27: ...evice error The following timing diagram shows how status information is registered at outputs SIo0 SIo3 based on a device error Key Message is displayed constantly Message is displayed briefly 200 ms...

Page 28: ...l e c t e d t t Fig Timing diagram for Operating mode selected without transponder key Operating mode selected with a transponder key that does not have permission for the selected operating mode SIo...

Page 29: ...key is not inserted in time before the operating mode is selected SIo0 SIo3 Pushbutton 2 N o a u t h o r i s a t i o n Ch 8h O M 1 s e l e c t e d Key mode 02 8h O M 1 s e l e c t e d t t 5h T r a n...

Page 30: ...Pushbutton operated for too long Pushbutton operated for too long with Key Mode 01 Key Mode 04 permissions or Pushbutton operated for too long with Key Service permission SIo0 SIo3 P u s h b u t t o n...

Page 31: ...m 16 is used to download the Key ID number to a controller 5 6 1 Key ID number serial number of the transponder key The Key ID number serial number is used to clearly identify the transponder key and...

Page 32: ...number The unique Key ID number for the relevant transponder key is downloaded to the higher level process controller using a defined protocol depending on the coded communication mode The communicati...

Page 33: ...Brief description of ap plication Assignment control sys tem Coding IDo0 IDsync Input No coding required IDo1 IDclock Input IDo2 IDout0 Input IDo3 IDout1 Input IDi0 IDin0 Output IDi1 IDin1 Output 5 6...

Page 34: ...de In advanced communication mode the download of the Key ID number behaves in the same way as the handshake controlled mode It differs from the handshake controlled com munication mode in so far that...

Page 35: ...IDclock b max 100 ms Bit 13 Bit 11 Bit 02 Bit 11 Bit 00 IDout1 Bit 12 Bit 27 Bit 25 Bit 16 Bit 15 Bit 14 IDin0 Bit 26 Bit 13 Bit 11 Bit 02 Bit 11 Bit 00 IDin1 Bit 12 T a min 60 ms f e Fig Timing diagr...

Page 36: ...out0 and IDout1 is present and valid and can be read by the controller c By the falling edge at IDclock test pulse line the controller must send the previously read bit back to the PIT m4SEU via the d...

Page 37: ...0 AND IDout1 Increment Bit Counter Set IDin0 IDout0 Set IDin1 IDout1 IDclock 0 No Bit Counter 14 End No Clear Bit Counter Last Bit Timer 60ms Start Last Bit Timer No b c d e a See Fig Timing Diagramm...

Page 38: ...e signal is generated by the PIT m4SEU and indicates whether a data bit at IDdata is valid invalid 0 signal The data bit at IDdata is invalid and may not be evaluated 1 signal The data bit at IDdata i...

Page 39: ...data bit at data line IDdata d 0 signal at IDrequest handshake line The controller confirms that it has read the requested data bit without error e 0 signal at IDresponse handshake line The PIT m4SEU...

Page 40: ...Function description Operating Manual PIT m4SEU 1004648 EN 02 40 Status diagram for handshake controlled signal download Fig Status diagram for handshake controlled signal download...

Page 41: ...quest 1 Set Bit Counter 0 Store ID Number IDresponse 1 No IDresponse 0 Time Control tIDend 200ms No Bit Counter 28 Start a b c d e Last Bit Control Data Read and Acknowledge Bit Request Requirement Se...

Page 42: ...tion is sent in accordance with the Interface for status information 23 Only transponder keys with permission 1 5 are registered on the PIT m4SEU With any other permissions the PIT m4SEU does not rece...

Page 43: ...display MSO release tack 2 MSO1 MSO1 MSO2 MSO1 MSO1 MSO2 MSO2 MSO1 selected 8h MSO1 selected 8h MSO2 selected 9h MSO2 selected 9h MSO1 MSO2 5h Ch 5h 0h Fig Changing the operating mode after operating...

Page 44: ...mode during an operating mode change depending on the process requirement Only the last operating mode preselection is confirmed by the control ler You can deactivate the function although it is confi...

Page 45: ...ontroller 0 signal at the keylock input Please note that removing the transponder key on the PITreader does not reset the operat ing mode preselection NOTICE The operating mode preselection is not a s...

Page 46: ...r to the table in Advanced communication mode 34 tack Acknowledge Time min 120 ms keylock Control signal is generated by the controller and must be present for at least 20 ms for the signal state to b...

Page 47: ...tall the device in a control cabinet or control console Use the notch on the rear of the device to attach it to a mounting rail 35 mm When installed vertically Secure the device by using a fixing elem...

Page 48: ...Installation Operating Manual PIT m4SEU 1004648 EN 02 48 25 2 9 5 37 2 80 266 Fig View from below...

Page 49: ...OM5 X2 A1 A2 Terminals for connecting the supply voltage SIo0 SIo3 Interface for status information Evaluation of status informa tion IDi0 IDi1 Key ID interface Inputs for receiving the input signals...

Page 50: ...nterface The PITreader is supplied from the 24V 0V voltage outputs on the PIT m4SEU in order to avoid potential differences The connections of RxD and TxD on the PIT m4SEU should be crossed The cable...

Page 51: ...ng on the selected communication mode connect the terminals of the Key ID interface to a controller that supports the download of the Key ID number or a Connect IDsync to a controller if all you wish...

Page 52: ...Wiring Operating Manual PIT m4SEU 1004648 EN 02 52 Connection for transmitter controlled communication mode Fig Connection for transmitter controlled communication mode example...

Page 53: ...Wiring Operating Manual PIT m4SEU 1004648 EN 02 53 Connection for handshake controlled communication mode Fig Connection for handshake controlled communication mode example...

Page 54: ...Wiring Operating Manual PIT m4SEU 1004648 EN 02 54 Connection for advanced communication mode Fig Connection for advanced communication mode example...

Page 55: ...in the event of an error at switch on NOTICE In the event of an error no active operating mode is displayed at the corres ponding display element and no semiconductor output has a 1 signal Behaviour...

Page 56: ...ted simultaneously when selecting an operating mode Procedure 1 Establish the connection with the transponder key a Insert a transponder key into the slot on the PITreader Note The transponder key mus...

Page 57: ...ure 1 Establish the connection with the transponder key a Insert the transponder key Key Service into the slot 2 Select special mode OM5 Service a Press pushbutton 1 OM1 Please note the required opera...

Page 58: ...gned output on the operating mode inter face switches to a 1 signal after the reaction time t2 has elapsed see Technical details 62 A defined switchover time t1 guarantees that only one operating mode...

Page 59: ...e PITreader operat ing manual Device error The DIP switch setting was changed during operation Invalid configuration via the DIP switch setting Delete error Please refer to the timing diagram for Devi...

Page 60: ...Display for pushbutton 1 Display for pushbutton 2 Display for pushbutton 3 Display for pushbutton 4 Meaning No supply voltage OM5 Service is active MSO5 has a 1 signal OM1 is active MSO1 has a 1 sign...

Page 61: ...ting mode is preselected OM5 is preselected but OM1 is still active MSO1 has a 1 signal Only when operating mode is preselected OM1 is preselected but OM5 is still active MSO5 has a 1 signal OM serves...

Page 62: ...urrent safe inputs 5 mA Input current standard inputs 3 mA Voltage at inputs 24 V DC Input current range 5 mA Galvanic isolation No Semiconductor outputs Overall performance ext loading semiconductor...

Page 63: ...mplitude 3 5 mm Acceleration 1g Shock stress In accordance with the standard EN 60068 2 27 Acceleration 15g Duration 11 ms Airgap creepage In accordance with the standard EN 61131 2 Overvoltage catego...

Page 64: ...ISO 13849 1 2015 PL EN ISO 13849 1 2015 Category EN 62061 SIL CL EN 62061 PFHD 1 h IEC 61511 SIL IEC 61511 PFD EN ISO 13849 1 2015 TM year PL d Cat 3 SIL CL 2 6 49E 09 SIL 2 3 99E 04 20 Explanatory n...

Page 65: ...r just one pushbutton Cat 2 can be estimated for the subsystem pushbutton the following conditions are met Demand rate Test rate 1 to 1 Testing occurs immediately upon demand of the safety function an...

Page 66: ...sure medium prevention of dirt intake drainage of compressed air e g in compliance with the component manufacturers requirements concerning purity of the pressure medium NOTE For combined fluidic and...

Page 67: ...Product type Features Order no PITreader base unit RFID authentication system base unit Required accessories PITreader key adapter 402 255 PITreader key ad apter h 1x PITreader key adapter horizontal...

Page 68: ...e products meet the requirements of the directive 2006 42 EC for ma chinery of the European Parliament and of the Council The complete EC Declaration of Conformity is available on the Internet at www...

Reviews: