PNOZ X9
Operating Manual PNOZ X9
19526-EN-09
18
Relay outputs
774601
774605
Utilisation category of auxiliary con-
tacts
AC15 at
230 V
230 V
Max. current
5 A
5 A
DC13 (6 cycles/min) at
24 V
24 V
Max. current
7 A
7 A
Utilisation category in accordance
with UL
Voltage
240 V AC G. P.
240 V AC G. P.
With current
8 A
8 A
Voltage
24 V DC Resistive
24 V DC Resistive
With current
5 A
5 A
Pilot Duty
B300, R300
B300, R300
External contact fuse protection,
safety contacts
In accordance with the standard
EN 60947-5-1
EN 60947-5-1
Max. melting integral
240 A²s
240 A²s
Blow-out fuse, quick
10 A
10 A
Blow-out fuse, slow
6 A
6 A
Blow-out fuse, gG
10 A
10 A
Circuit breaker 24V AC/DC,
characteristic B/C
6 A
6 A
External contact fuse protection,
auxiliary contacts
Max. melting integral
240 A²s
240 A²s
Blow-out fuse, quick
10 A
10 A
Blow-out fuse, slow
6 A
6 A
Blow-out fuse, gG
10 A
10 A
Circuit breaker 24 V AC/DC,
characteristic B/C
6 A
6 A
Contact material
0,2 µm Au
0,2 µm Au