PZE X5
Operating Manual PZE X5
1003301EN05
9
}
Contact malfunction: As the contact block is connected to a base unit,
reactivation will not be possible if the contacts have welded after the input circuit has
opened.
}
Open circuit, short circuit or earth fault ( e.g. in the input circuit)
Dimensions in mm
121 (4.76")
75 (2.95")
87 (3.42")
45
(1.77")
Technical details
General
774595
Approvals
CCC, CE, EAC (Eurasian), TÜV, cULus Listed
Electrical data
774595
Supply voltage
Voltage
24 V
Kind
DC
Voltage tolerance
15 %/+10 %
Output of external power supply (DC)
3,5 W
Residual ripple DC
20 %
Continuous duty
100 %
Max. overall cable resistance Rlmax
Singlechannel at UB DC
120 Ohm
Dualchannel without detection of shorts across
contacts at UB DC
240 Ohm
Dualchannel with detection of shorts across con
tacts at UB DC
4 Ohm
Voltage at
Input circuit DC
24,0 V
Current at
Input circuit DC
35,0 mA
Number of output contacts
Safety contacts (N/O), instantaneous
5