Operating Manual PZW
19157-EN-07
19
Relay outputs
774042
774044
774048
External contact fuse pro-
tection, safety contacts
In accordance with the
standard
EN 60947-5-1
EN 60947-5-1
EN 60947-5-1
Max. melting integral
240 A²s
240 A²s
240 A²s
Blow-out fuse, quick
6 A
6 A
6 A
Blow-out fuse, slow
4 A
4 A
4 A
Blow-out fuse, gG
6 A
6 A
6 A
Circuit breaker 24V
AC/DC, characteristic
B/C
4 A
4 A
4 A
External contact fuse pro-
tection, auxiliary contacts
Max. melting integral
240 A²s
240 A²s
240 A²s
Blow-out fuse, quick
6 A
6 A
6 A
Blow-out fuse, slow
4 A
4 A
4 A
Blow-out fuse, gG
6 A
6 A
6 A
Circuit breaker 24 V
AC/DC, characteristic
B/C
4 A
4 A
4 A
Conventional thermal cur-
rent
6 A
6 A
6 A
Contact material
0,2 µm Au
0,2 µm Au
0,2 µm Au
Times
774042
774044
774048
Recovery time at max.
switching frequency 1/s
After power failure
80 ms
80 ms
80 ms
Delay time tv
0,05 s, 0,1 s, 0,2 s, 0,3 s,
0,4 s, 0,5 s, 0,7 s, 1 s, 1,5
s, 2 s, 2,5 s, 3 s
0,05 s, 0,1 s, 0,2 s, 0,3 s,
0,4 s, 0,5 s, 0,7 s, 1 s, 1,5
s, 2 s, 2,5 s, 3 s
0,05 s, 0,1 s, 0,2 s, 0,3 s,
0,4 s, 0,5 s, 0,7 s, 1 s, 1,5
s, 2 s, 2,5 s, 3 s
Time accuracy
-15% / +15% +50 ms
-15% / +15% +50 ms
-15% / +15% +50 ms
Repetition accuracy
2 %
2 %
2 %
Max. delay time
tv + 15 % + 50 ms
tv + 15 % + 50 ms
tv + 15 % + 50 ms
Environmental data
774042
774044
774048
Climatic suitability
EN 60068-2-78
EN 60068-2-78
EN 60068-2-78
Ambient temperature
Temperature range
-10 - 55 °C
-10 - 55 °C
-10 - 55 °C
Storage temperature
Temperature range
-40 - 85 °C
-40 - 85 °C
-40 - 85 °C
Climatic suitability
Humidity
93 % r. h. at 40 °C
93 % r. h. at 40 °C
93 % r. h. at 40 °C
Condensation during op-
eration
Not permitted
Not permitted
Not permitted
EMC
EN 60947-5-1, EN
61000-6-2, EN 61326-3-1
EN 60947-5-1, EN
61000-6-2, EN 61326-3-1
EN 60947-5-1, EN
61000-6-2, EN 61326-3-1