Commissioning
Operating Manual PNOZ s30
1001715-EN-15
52
Other, pre-defined settings:
}
Switch functions
–
Direction (F3)
Left direction
Tolerance for wrong direction = 10 pulses
–
Direction (F4)
Right direction
Tolerance for wrong direction = 10 pulses
}
Parameter set/select input
P0, select inputs are ignored (Select inputs mode: "None ")
}
Hysteresis
Standstill and speed, 2 % each
}
Output assignment
–
Standstill: Relay output Rel. 1 and semiconductor output Out 1
–
Speed: Relay output Rel. 2 and semiconductor output Out 2
–
Left direction: External output Ext. 1 and semiconductor output Out 3
–
Right direction: External output Ext. 2 and semiconductor output Out 4
}
Start mode
–
All outputs: Automatic start ("Automatic")
}
Switch delay
None
}
Max. encoder frequency
1 MHz