PSEN cs1.19n
Operating Manual PSEN cs1.19n
1003269-EN-04
14
PNOZmulti
I0
I1
12
22
1
3
A1
A2
0
V
2
4
V
4
2
5
PNOZmulti
PSENcode
n.c.
Fig.: Selection in the PNOZmulti Configurator PSENcode with three actuators as an example
Legend
I0 Input OSSD
I1 Input OSSD
Teaching in the actuator
Any Pilz actuator PSEN cs1.19) is detected as soon as it is brought into the response
range.
Installation
CAUTION!
The unit's properties may be affected if installed in an environment contain-
ing electrically or magnetically conductive material. Please check the oper-
ating distances and the assured release distance.
}
The safety switch and actuators should be installed opposite each other in parallel.
Make sure that all the actuators are in the position intended for operating the safety
switch, parallel to the safety switch.
}
Safety switches and actuators should be permanently secured using M5 safety screws
with a flat head (e.g. M5 cheese-head or pan head screws).
}
Protect the actuator from contamination.
}
Torque setting: Please note the information provided under
Technical details [
18]
.
}
The distance between two safety switches must be maintained (see
Technical
details [
18]
).
}
Make sure that the safety switch and actuator cannot be used as an end stop.