PIT es Set10u-5ns (AIDA) basic
Operating Manual PIT es Set10u-5ns (AIDA) basic
1004863-EN-03
| 15
To connect a decentralised module (e.g. PDP67 F 8DI ION from Pilz), use a 5-pin unshiel-
ded cable with an A-coded M12 male connector (for connection to the decentralised mod-
ule) and an A-coded M12 female connector (for connection to the E-STOP device) (see
Or-
der reference [
20]
"Connection cable for connection to decentralised modules").
Examples for connection to Pilz evaluation devices
Evaluation device
Internal supply voltage
External supply voltage (24 V)
PNOZ s5
PIT es Set10u-5ns
basic
(400 463)
S11
A2
S21
2
1
3
4
5
PNOZ s5
S22
S12
PNOZ m B0
T0
M20
A2
2
1
3
4
5
PNOZ m B0
T1
M21
IM0
IM1
PIT es Set10u-5ns
basic
(400 463)
A2
2
1
3
4
5
PNOZ m B0
IM0
IM1
L+
PIT es Set10u-5ns
basic
(400 463)
PDP67 F 8DI ION
2
1
3
4
5
PDP67 F 8DI ION
2
1
3
4
5
PIT es Set10u-5ns
basic
(400 463)
NOTICE
Check wiring
Particularly if you are using an open-ended cable, check the function of the
E-STOP pushbutton before commissioning the plant/machine by interrupt-
ing the GND connection of PIN 3. The evaluation device must then switch
off. When an evaluation device does not switch off, there is a wiring error.