Requirements and connection to evaluation devices
For use of PIT es Set10u-5ns (AIDA) basic an evaluation device must be connected.
Connect the PIT es Set10u-5ns (AIDA) basic
}
either with a Pilz evaluation device
}
or with an evaluation device with defined properties (see section Defined properties of
evaluation devices:)
Suitable Pilz evaluation devices are, for example:
}
PNOZelog for E-STOP monitoring
– PNOZ e1.1p (Order No. 774 133)
}
PNOZ X for safety gate monitoring
– PNOZ X2.8P (Order No. 777 301 and 787 301)
}
PNOZsigma for safety gate monitoring
– PNOZ s5 (Order No. 750 105 and 751 105)
}
PNOZmulti for E-STOP monitoring
– PNOZ m B0 (Order No. 772 100)
}
PSSuniversal
– PSSu E F 4DI (Order No. 312 200)
}
Decentralised periphery
– PDP67 F 8DI ION (Order No. 773 600)
Defined properties of evaluation devices:
}
Dual-channel with detection of partial operation (only one channel of the input circuit is
open)
}
Detection of shorts across contacts and earth fault detection: Detection of shorts across
contacts is possible also via a positive and negative input circuit
}
Digital inputs type 2 in accordance with IEC 61131-2
}
Offset test pulses (not overlapping) with a maximum duration of the on/off test pulse of
7.5 ms
Connect the evaluation device as described in the evaluation device’s operating manual.
Please note:
}
Protective separation of the outputs to voltages over 60 V
}
The power supply that feeds the evaluation device must meet the regulations for PELV in
accordance with EN 60204-1.
}
The evaluation device must meet the requirements in the
Technical details [
18]
. The
specified values must not be exceeded.
}
The LED safety printed circuit board built into the unit contains two permanently installed
blow-out fuses. If the fuses are tripped by overcurrent or overvoltage, the LED safety prin-
ted circuit board must be exchanged (see
Order reference [
20]
).
Ensure the wiring and EMC requirements of IEC 60204-1 are met.
To connect the evaluation device to the E-STOP device, use a 5-pin unshielded cable with
an A-coded M12 female connector (see
Order reference [
20]
"Open-ended connection
cable").