Technical details
Operating Manual PCOM sec br2
1004534-EN-04
| 46
Environmental data
Climatic suitability
In accordance with the standard
EN 60068-2-30, EN 60068-2-78
Humidity
93 % r. h. at 40 °C
Condensation during operation
Not permitted
Max. operating height above sea level
2000 m
EMC
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN
61000-4-5, EN 61000-4-6, EN 61000-6-4, EN
61131-2
Vibration
In accordance with the standard
EN 60068-2-6
Frequency
5 - 8,4 Hz, 8,4 - 150 Hz
Amplitude
3,5 mm
Acceleration
1g
Shock stress
In accordance with the standard
EN 60068-2-27
Acceleration
15g
Duration
11 ms
Airgap creepage
In accordance with the standard
EN 61131-2
Overvoltage category
II
Pollution degree
2
Rated insulation voltage
30 V
Protection type
In accordance with the standard
EN 60529
Housing
IP20
Terminals
IP20
Mounting area (e.g. control cabinet)
IP54
Potential isolation
Potential isolation between
Periphery supply and module supply
Type of potential isolation
Basic insulation
Rated surge voltage
2500 V
Mechanical data
Mounting position
vertical
DIN rail
Top hat rail
35 x 7,5 EN 50022
Recess width
27 mm
Material
Bottom
PC
Front
PC
Connection type
Spring-loaded terminal, screw terminal
Mounting type
plug-in
Conductor cross section with screw terminals
1 core flexible
0,25 - 2,5 mm², 24 - 12 AWG
2 core with the same cross section, flexible without
crimp connectors or with TWIN crimp connectors
0,2 - 1,5 mm², 24 - 16 AWG