
Function description
Operating Manual PCOM sec br2
1004534-EN-04
| 17
}
The VPN connection can be controlled via a digital input.
}
The VPN connection can be signalled via an LED.
5.3
Input and output
The SecurityBridge provides a digital input and a digital output. These can be used for vari-
ous functions, as required.
The following functions can be configured on the user interface:
}
Functions digital input:
– SSLVPN
Access to the SecurityBridge via a VPN connection is controlled via the digital input.
New VPN connections can only be created when there is a 1-signal at the input or, in
the case of an inverted input, a 0-signal. The connection is broken as soon as the
configured signal is no longer present at the input.
– SETUP MODE
Setup mode can be activated via the digital input. Setup mode is active when there is
a 1-signal at the input or, in the case of an inverted input, a 0-signal.
}
Functions digital output
– SSLVPN
A VPN connection is signalled via the digital output. If there is a 1-signal at the output,
then there is at least one VPN Client connected. If there is a 0-signal at the output,
then no VPN Client is connected.
– BYPASS
Bypass mode is signalled via the digital output. If there is a 1-signal at the output,
then bypass mode is activated. If there is a 0-signal at the output, then bypass mode
is not activated.
– CRC
A change to the check sum is signalled via the digital output. If there is a 1-signal at
the output, then at least one project check sum no longer matches the configured
check sum. If there is a 0-signal at the output, then no check sum has changed.
Please note that in the menu Security functions the option
Check sum monitoring
must be configured.
– DEVMON
Device monitoring is signalled via the digital output. If there is a 1-signal at the output,
then at least one device that has been configured for monitoring is no longer access-
ible. If there is a 0-signal at the output, then all devices are accessible.
Please note that in the menu Security functions the option
Device monitoring
must
be configured.
– SETUP MODE
Setup mode is signalled via the digital output. If there is a 1-signal at the output, then
setup mode is activated. If there is a 0-signal at the output, then setup mode is not ac-
tivated.