8.6.1 Real-time data register list
Regist
er
addres
s
Read/w
rite
attribut
e
Definition
Data
Type
Description
40001
RO
Phase A voltage
UINT16
Secondary side L-N
voltage, Calculation
factor: 0.01,
unit: V
40002
RO
Phase B voltage
40003
RO
Phase C voltage
40004
RO
Line AB voltage
UINT16
Secondary side L-L
voltage, Calculation
factor: 0.01,
unit: V
40005
RO
Line BC voltage
40006
RO
Line CA voltage
40007
RO
Phase A current
UINT16
Secondary Side current,
Calculation factor: 0.001,
unit: A. If use CT, then
customers need to
multiply by CT ratio.
40008
RO
Phase B current
40009
RO
Phase C current
40010
RO
Neutral current
40011
RO
Total active power low word
LINT32
Secondary side active
43