7. Technical Datasheet
Parameters
range
Rated
operating
parameters
Rated Power Supply
AC 85~265V
DC 100~300V
Rated input current
5A or 1A
Rated input voltage
3×220/380V 35Hz~65Hz
Status input
Rated voltage
220V
,
2 channel active status input, less than
60V is open, more than 140V is closed
,
Max.
Input is 300V.
Relay output
Rated contact
capacity
AC 250V/5A or DC 30V/5A
parameter
range
Accuracy
Accuracy of
electric
parameters
voltage 10%~150% 0.5%
current 1%~120%
0.5%
Power factor
-1~1
1%
Active energy
0~99999999.9
0.5%
Reactive energy
0~99999999.9
2%
Active power
Single phase
:
0 ~ ±
26MW/var/VA
Total
:
0 ~ ± 78MW/var/VA
0.5%
Reactive power
1.0%
Three-phase current
unbalance
0%~100% 1%
Harmonic content
0%~100%
B
级
parameters
Performance
Power
Consumption
≤
2W/5VA
Cabinet
temperature
Normal operating
temperature
-10
℃
~
+55
℃
Limit operating
temperature
-25
℃
~
+55
℃
Storage temperature
-40
℃
~
+70
℃
Relative humidity
5
%~
95% RH, non-condensing
Insulation
ability
Power frequency
withstand voltage
2000VAC
Insulation resistance
≥
100M
Ω
Impulse voltage
6000V
IP index
front panel
IP52
25