6.3 Dual Source kWh measurement
DI 1 be defined as special function (register 40207), as dual source kWh
measurement function
After start this function:
If DI 1 with status of ON, add energy value to Grid area (register 40052-40063),
on the display will show Grid. And the value also will add to register
40026-40037.
If DI 1 with status of OFF, add total energy value to Generator area (register
40064-40075), on the display will show Gen. And the value also will add to
register 40026-40037.
Customer can query total energy, Grid energy and Gen energy from the page of
kWh (Active/ Reactive)