20
there is a new command that makes the relay operates, the timer will
restart.
-
Local control: When an alarm signal activating the relay is generated,
the relay operates. The relay’s operating status will be kept within the
period of time for timing. When the timer overflows, the relay will be
released and kept released.
7. Setpoint Alarm
PMAC615 provides one relay alarm output which is programmable.
When the relay output is set to in local control mode, it indicates corresponding set point
alarm. There are 5 parameters may be set under setpoint alarm feature.
Refer to below
sheet:
Operation object
0 - Prohibit
1 – Voltage
2 – Current
Operation upper limit value
0% - 120% of rating
Operation lower limit value
0% - 120% of rating
Operation time delay
0 - 1200s, 0 means the relay operates
immediately.
Return time
0 - 1200s, 0 means non-return.
Suppose that, Users want to know if there is undervolatge situation. It is required that if in
undervoltage situation, it alarms immediately, until normal voltage is resumed.
The
programming procedure as follow:
Operation object: Voltage