6.2.3
M-Bus Master options
The parameters belongs to the unit itself will be handled under this caption.
6.2.3.1
myprimaryaddress
PiiGAB M-Bus 900S/T is functioning as an M-Bus meter on the M-Bus network with the internal
master address set to 251. The address 251 is according to the M-Bus standard used for
intelligent M-Bus masters. The address can be changed by writing in a new primary address
between 0-
250 in the field ”myprimaryaddress.”
6.2.3.2
Switchblocktime
The parameter ”switchblocktime” controls the exchange between the different slave ports to the
master port. When the meter has left an answer the Pi-900S/T
”switchblocktime” is waiting for a
new question to the same meter if it is a multitelegram question. If no question arrives the next
question in line will be let through.
Default setting 200ms