T H E M O D E R M - B U S T E C H N O L O Y
61
Ve
rs
io
n E
.3
.0
1.0
0
9.4.5
Reset command SND_NKE
Table 9-7
Byte No
Size (byte)
Value (Hex)
Description
1
1
10
Start character
2
1
40
C-field, REQ_UD2
3
1
xx
A-field, address (Default 251, Hex FB)
4
1
xx
CS checksum
5
1
16
End character
9.4.6
Reset passed
Table 9-8
Byte No
Size (byte)
Value (Hex)
Description
1
1
E5
Transmission passed
9.4.7
Application reset
Table 9-9
Byte No
Size (byte)
Value (Hex)
Description
1
1
68
Start character
2
1
03
L- field
3
1
03
L- field
4
1
68
Start character
5
1
53/73
C- field, SND_UD
6
1
xx
A- field, address (Default 251, Hex FD)
7
1
50
CI- field
8
1
xx
CS checksum
9
1
16
End character
9.4.8
Application reset passed
Table 9-10
Byte No
Size (byte)
Value (Hex)
Description
1
1
E5
Transmission passed