82 East Main Street Suite 3.14 • Webster, NY 14580 Tel: 585.872.9350 • Fax: 585.872.2638 • [email protected] • www.piecal.com

Page 1

•  

EASY TO USE

With the PIECAL 434 you can check, calibrate and measure all your current signal instruments 

in a 4 to 20 milliamp DC loop. It can be used at any access point in your loop. Source & Read 

0.000 to 24.000 mA, Simulate a 2 Wire Transmitter or use the PIECAL 434 to simultaneously 

power your 2 Wire Transmitter and measure its output. 

•  

EASY TO READ

Turn on the backlight to easily read the display in 

dark areas of the plant.

•  

TROUBLESHOOT LOOP PROBLEMS

Quickly diagnose ground fault and current 

leakage with the patented loop diagnostic 

technology (US Patent# 7,248,058).

•   SOURCE MILLIAMPS

Calibrate recorders, digital indicators, stroke 

valves or any instruments that get their input 

from a 4 to 20 mA loop. Easily set any value 

quickly to within 0.001 mA with the adjustable 

digital potentiometer “

DIAL

” or use preset 

4.000 

mA (0.00%)

 and 

20.000 mA (100.00%)

 

EZ-CHECK™ settings.

•   AUTOMATIC OUTPUT STEPPING & RAMPING

Press & hold the dial to automatically step from 4 

to 20 in 2, 3 or 5 steps or choose a continuous 

ramp.

•  CALIBRATE USING LOOP POWER

Check loop wiring and receivers by using the 

PIECAL 434 in place of a 2 Wire transmitter. The 

PIECAL 434 uses any loop power from 2 to 60 V 

DC.

•   READ LOOP CURRENT

Check controller outputs or measure the milliamp 

signal anywhere in the loop. The PIECAL 434 

measures 0.000 to 24.000 mA (-25.00 to 125.00%) 

signals with greater accuracy than a typical multimeter. 

•   POWER & MEASURE 2 WIRE TRANSMITTERS

The PIECAL 434 can simultaneously output 24V DC to power any and all devices in a process 

loop using the internal batteries and internal switching power supply, while measuring the output 

of a 2 Wire Transmitter and any other loop devices. Powers HART™ transmitters with built-in 250 

ohm resistor simplifying hookups with HART communicators.

•   READ DC VOLTS

The PIECAL 434 can measure from -60.00 to +60.00 VDC with 10mV resolution. Use it to check 

loop power supplies, I/V converters, 1 to 5 Volt signals, and other voltages making it 

unnecessary to carry an additional multimeter.

Copyright © 2011 All rights reserved  • 434-9002 - Rev C 13 July 2011

PIECAL 434

Automated Diagnostic 4-20 mA Calibrator

 

Operating Instructions

PIECAL 434

Automated Diagnostic 4-20 mA Calibrator

 

Operating Instructions

www.

.com

[email protected]

1.800.561.8187

Summary of Contents for PIECAL 434

Page 1: ...om 4 to 20 in 2 3 or 5 steps or choose a continuous ramp CALIBRATE USING LOOP POWER Check loop wiring and receivers by using the PIECAL 434 in place of a 2 Wire transmitter The PIECAL 434 uses any loo...

Page 2: ...put 0 001 mA 0 01 at a time Push and turn the knob for faster dialing adjusting 0 100 mA 1 00 at a time Press and Hold the knob to start automatic stepping or ramping Double click the knob for steppin...

Page 3: ...0 5 steps between 4 8 12 16 20 mA 0 25 50 75 100 RAMP will continuously ramp the output between 4 20 mA 0 100 GROUND LEAK DETECTION when ON the PIECAL 434 has the ability to check for current leaks ca...

Page 4: ...4mA 20mA or 20mA 4mA for 30 seconds then reverse direction Stop the stepping or ramping by pressing or turning the knob or moving any switch Sourcing Milliamps Power 2 Wire Transmitters Dial Output to...

Page 5: ...l automatically step or ramp between 4mA 20mA or 20mA 4mA for 30 seconds then reverse direction Stop the stepping or ramping by pressing or turning the knob or moving any switch To Sensor Typical 2 Wi...

Page 6: ...DC are indicated by ion the display Signals exceeding 99 99 VDC will be indicated by OVERRANGE flashing on the display Read DC Volts Voltage to be Measured Battery Loop Power Supply Transmitter Voltag...

Page 7: ...e PIECAL 434 to the plus input of the device and the black source lead to the minus The PIECAL 434 supplies a nominal 24 volts DC at 24 mA to the 2 Wire Transmitter The current passed by the transmitt...

Page 8: ...an indication of leakage current at the bottom of the display If there is an uncontrolled loop a transmitter with upscale burnout and bad or missing sensor or a short the display shows iLOOP 24mA Note...

Page 9: ...E SIGNALS Signals below 0 mA or open circuits are indicated by 0 000 mA 25 00 on the display Signals above 24 mA are current limited by protection circuitry to approximately 25 mA OPEN LOOPS The displ...

Page 10: ...t the 4 20 mA control wires from the Current to Pressure I P converter or the actuator 2 Connect the PIECAL 434 following the connection diagrams on the previous pages for Simulate 2 Wire Transmitters...

Page 11: ...VAC for North America Only charger four NiMh batteries AC DC cords Part 020 0103 Low Battery Low battery indication with nominal 1 hour of operation left Protection against misconnection Over voltage...

Page 12: ...Accuracy Same as Source Power Measure Voltage burden 2V at 20 mA Overload Current limit protection 24 mA nominal Loop voltage limits 2 to 60 VDC fuse less protected from reverse polarity connections...