![PicoBox REX User Manual Download Page 28](http://html1.mh-extra.com/html/picobox/rex/rex_user-manual_1555410028.webp)
Linkwise Technology Pte Ltd REX User Manual
IO Configuration
Authorized users can change IO configuration description and alarm state by sending the commands below.
SMS Remote
Action
SMS Command
Sample Command
Comment
Rights
Operation
Authorizer
Add /
Replace Input
description
#ipd N,d,o,c
#ipd
1,UPS,Normal,Alarm
N = input 1- 8
d = description
o = open state
c = close state
no
yes
#ipd
1,UPS,Alarm,Normal
Add /
Replace
Output
description
#opd N,d
#opd 1,siren
N = output 1 or 2
no
yes
Set / Change
Input alarm
state
#ipa N,input_alarm
#ipa 1,close
N = input 1 - 8
no
yes
#ipa 2,open
input_alarm = none
or open or close
Set / Change
Analog Input
settings
#aic N,d,u,el,eh,h,o
#aic
1,Battery,Volts,0,12,2,
0
N = Analog input 1-2
d = Description;
u = Unit
el = Engrg Low
eh = Engrg High
h = Hysteresis
o = Offset
no
yes
Set / Change
Analog Input
alarms
#aia N,l,h
#aia 1,25,36
N = Analog input 1-2
l = low alarm val
h = high alarm val
no
yes
Enable /
Disable
Analog Input
alarms
#aie N,le,he
#aie 1,0,1
N = Analog input 1-2
le = low alarm
enable
he = high alarm
enable
no
yes
Table 12.5 I/O Configuration
Repeat Configuration
Authorized users can change the SMS alarm repeat settings sending the commands below. To cancel
repeat sending, any mobile phone from the operation or forward must acknowledge to REX by replying the
acknowledge command (
#ack
).
SMS Remote
Action
SMS
Command
Sample
Command
Comment
Rights
Operation
Authorizer
Set number of
repeat times
#rpt N
#rpt 2
N = number of times
SMS repeat
no
yes
#rpt 0
0= disable repeat
Set repeat
interval
#rpt-time N
#rpt-time 5
N = repeat time interval
in minutes
no
yes
Query repeat
status
?rpt
?rpt
System reply with repeat
interval
yes
yes
Acknowledge
repeat alarm for
DIn (Xn) or AIn
(An)
#ack Xn | An
#ack X1
System reply with Ack
received. Sms repeat
stops
yes
yes
Table 12.6 Repeat Configuration