O P E R AT I N G A N D I N STA L L AT I O N I N ST R U CT I O N S SYST E M V E N T E C H LG 5 0 0 P
PAG E 2 1
Ventilation unit
Dimensions (W x H x D)
915 x 855 x 720 mm Housing of single-
shell construction made of galvanized
sheet steel, coated in RAL 9010 – white,
25 mm/30 mm of heat insulation.
Air line connection
4x ø 200 mm
Condensate connection
ø 15 mm at the bottom
Electrical connection:
230 V/50 Hz/16 A
Protection class:
IP 20
Permitted ambient temperature
+5 °C to +40 °C
Permissible air temperatures
-15 °C to +35 °C
Weight without accessories
approx. 75 kg
Operator control unit „PI-HMI“
Dimensions (W x H x D)
80 x 121 x 42 mm
If mounted in the room, a connecting
cable to the power unit is required:
MPFK6S – or similar 6-core flat cable.
The cable length must not be longer
than 50 m.
Air filters
Outdoor air/supply air filter
Pocket filters quality category F7,
optional quality category F9
Extract air filter
Pocket filters quality category G4
Fans (factory setting)
Fan speed
Speed I
Speed II
Speed III
Air volume
flow [m³/h]
200
300
400
Output in
[W] with
external
50/100 Pa
50/65
80/100
130/155
Air volume flow setting range 150 to 550
m³/h, settable in increments of 5 m³/h.
Flow efficiency in accordance with PHI
0.33 W/m³/h. Power consumption in
standby mode 6.5 W
For the purpose of ensuring safe opera-
tion of the system the safety devices and
covers must not be put out of service,
bypassed or dismantled by any measu-
res.
The system must be shut down imme-
diately if faults or malfunctions occur in
the ventilation system that could pose a
risk to persons or property.
Further operation must be effectively
prevented until a complete repair has
been made! Repair may only be perfor-
med by a skilled installer.
Overheating protection.
A thermo bi-metal switch is
built in to protect the optio-
nally-integrated frost protection heater
battery from overheating. When a tem-
perature of +50 °C is reached, this
element interrupts the power supply to
the PTC electric heater battery.
4.7 SAFETY DEVICES
5 Technical specifications
5.1 UNIT SPECIFICATIONS
Illustration: PTC low temperature preheater battery