7. Condensate tank with discharge fitting

 

Any condensate incurred in the heat 
exchanger during operation is collected 
via the condensate trough.  
The condensate incurred is discharged 
via the connected condensate drainage 
system, which is routed via an
effective odour trap. 
 

8. Frost protection heating with a PTC low 
temperature preheater battery (optional) 

In very cold outdoor air temperatures, 
protects against freezing of condensate 
in the heat exchanger. The outdoor air is 
pre-heated, depending on the outdoor air 
temperature, via the optional electrical 
PTC lowtemperature pre-heater battery. 
 
 

If a water battery or brine bat- 

 

tery is used for frost protection  

 

the heat exchanger, the battery 

has to be protected in a suitable way 
against freezing when there is frost. 
 

9. Bypass valve with actuator

 

The 100% bypass is controlled as a func-
tion of the preset room temperature, the
measured extract air temperature
and the outdoor air temperature. As 
a result the heat exchanger can be 
circumvented in the summer and the 
cool outdoor air blown out at night either 
directly or via the earth collector into the 
living space. 
 

10. Outdoor air and supply air fan

 

Ensures the air volume flow for the sup-
ply air; provides the living spaces with 
conditioned outdoor air. 

11. Exhaust air and extract air fan 

Ensures the air volume flow for the 
extract air; conveys the consumed air 
externally out of the apartment. 
 

12. Pressure sensor for volume flow 
constant function (optional)  

Measured value sensor and pressure 
sensors for the optional definable volu-
me flow constant function of the fans.  
 

13. Exhaust-air-side sound absorber 
insert (optional) 

For noise reduction in the vicinity of the 
exhaust air fan. 
 

14. Front cover with an over-center 

latch

 

The front cover can be easily opened 
for maintenance work to the device, e.g. 
filter exchange. When closing it, make 
sure of complete fastening and sufficient 
seal tightness between the front cover 
and the unit’s housing. 
 

15. Air line connection 

Is for the purpose of connection to the 
air line system. When installing, ensure 
correct connection to the supply, extract, 
outdoor air and exhaust air lines.  
 

16. Cable inlets  

Fundamentally the ventilation unit is 
supplied electrically ready wired. The 
cable inlets are used for making the 
electrical connection, for connecting the 
operator control unit and the optional 
system accessories, for example, tempe-
rature sensors etc. 

Summary of Contents for Ventech LG 150

Page 1: ...ble when controlled to local requirements and is valid up to the speci ed maximum air ow volume EU Regulation 1253 2014 ErP 2018 2016 1254 2014 ENERGIA ENERGIJA ENERGY ENERGIE E Z LG 500 W A 42 dB 445...

Page 2: ...ERNAL AUXILIARY HEATING PAGE 15 4 4 OPTIONAL DEMAND DRIVEN PLANT OPERATION PAGE 15 4 5 OPTIONAL BUILDING AUTOMATION NETWORKING PAGE 16 4 6 VENTILATION UNIT PAGE 17 4 7 SAFETY DEVICES PAGE 21 5 Technic...

Page 3: ...10 1 PREREQUISITES FOR INSTALLATION OF THE UNIT 35 10 2 DEVICE INSTALLATION PAGE 36 10 3 ELECTRICAL CONNECTION PAGE 39 10 4 INITIAL STARTUP PAGE 41 11 Servicing and cleaning Page 42 11 1 SAFETY DIREC...

Page 4: ...type PI HMI READ THESE INSTRUCTIONS CAREFULLY BEFORE INITIAL STARTUP OF THE UNIT These instructions contain advice and information about the safe operation ins tallation service and maintenance of the...

Page 5: ...uitable experience and or knowledge unless supervised by a person who is responsible for their safety or from whom they receive inst ructions on how to use the device The unit is not suitable for inst...

Page 6: ...TECH may not be removed without prior written approval of the ma nufacturer The manufacturer accords a warranty on spare parts only if they have been installed by an installer who is recognized by the...

Page 7: ...dangerous electrical voltage The non observance of this warning can lead to injury or danger to life and limb Installation commissioning maintenance and repair must be performed by an authorised spec...

Page 8: ...of 5 C and a maximum of 40 C The device is intended for free standing installation or wall mounting and may only be set up when there is suitable load bearing oor or wall construction No vibrations m...

Page 9: ...in operation in the summer for hygienic reasons the air lters have to be repla ced before putting it back into operation In case of simultaneous use of the ven tilation unit with replaces consuming in...

Page 10: ...optional 15 Suction element with pre lter G4 16 Heater battery for brine EHE earth heat exchanger optional 4 Functioning of the ventilation system In the case of mechanically controlled apartment vent...

Page 11: ...1 Frost protection via heat exchanger bypass If the ventilation unit has no pre heating exchanger a bypass may be used to pro tect the heat exchanger from freezing Cold outside air will in this case...

Page 12: ...fficiency alarm limit To trigger the alarm the system must be running the efficiency must be less than the set value and the alarm at low efficiency parameter must be set to Yes 4 2 2 Frost protection...

Page 13: ...temperature Motor driven valve Set the control range of the motor driven valve 0 10 V 2 10 V 4 2 3 Frost protection via electric pre heating exchanger optional The compact ventilation unit LG 500 P S...

Page 14: ...l heating exchanger P band P band for PI controller pre heater I time I time for PI controller pre heater 4 2 4 Heat exchanger The Air2 system may use various heat exchangers for heat recovery WRG Byp...

Page 15: ...STEM EXTENSION FOR EXTERNAL AUXILIARY HEATING The pumped hot water re heating exchanger PWW NHR mixer valves are controlled via 0 10 V signals continuous The circulating pumps will also be activated o...

Page 16: ...ducts The fan optimiser signal in nitely variable is connected to the analogue input The plant must be tted with 2 sepa rate fan optimisers one each in the supply and extract air ducts 4 4 3 GreenZon...

Page 17: ...e extract air with integrated wired control elect ronics and an optional PI HMI remote control panel for free standing or wall mounting in frost free rooms Ventilation unit with highly efficient energ...

Page 18: ...e the fan speed for ex ample can be increased individually air blast ventilation The PI HMI control unit can also be used to make individual operating parameter settings during servicing work 2 Contro...

Page 19: ...ther directly or via the earth collector into the living space 10 Outdoor air and supply air fan Ensures the air volume ow for the sup ply air provides the living spaces with conditioned outdoor air 1...

Page 20: ...d ventilation operation via CO2 sensor and or humidity sensor Version Right hand version Left hand version Part no without integrated PTC preheater battery 08LG500P R 08LG500P L Item no with an integr...

Page 21: ...ed Speed I Speed II Speed III Air volume ow m h 200 300 400 Output in W with external 50 100 Pa 50 65 80 100 130 155 Air volume ow setting range 150 to 550 m h settable in increments of 5 m h Flow eff...

Page 22: ...he characteristics illustrated are appli cable for the device design with supply air lter quality category F7 extract air lter quality category G4 and the design with PTC pre heater battery in bypass...

Page 23: ...4 20 26 30 35 40 16 21 26 8000 Hz 19 21 22 13 17 21 11 13 16 17 23 30 11 13 14 Total LWA in dB A 39 41 44 53 55 57 44 48 53 53 55 60 50 51 55 6 Operator control unit The settings made on the ventilati...

Page 24: ...er from those shown in these instructions 6 2 2 Fan speed To set fan speed press the fan in the lower part of the home screen You can choose between six prede ned fan speeds Off Auto Low Medium High a...

Page 25: ...icon in the upper right corner of the home screen Begin by pressing the menu icon in the upper right corner of the home screen The following screen is then displayed Home Press this icon to return to...

Page 26: ...r the whole week Daily program For each day different ventilation settings can be paramete rized Weekday weekend Ventilation set tings on weekdays and weekends are set 1 Switching between the differen...

Page 27: ...con on the home screen 6 2 4 4 Extended operation If a different pattern of operation is required for a short period of time the weekly program can be overridden The override period can last up to a w...

Page 28: ...ate in the settings and follow the instructions on the display 6 2 4 7 Settings The following can be set viewed Language Time date Locking of fan speed during adjust ment Setting of fan speed in case...

Page 29: ...ent Once the required air volume has been reached the fan is locked at its current speed This gives the installer the opportunity to adjust the system ensuring the right amount of air in the individua...

Page 30: ...PAGE 30 6 2 4 13 Factory reset PIN required Here you can restore factory settings 6 2 4 14 Home PIN required Here you can con gure the icons shown in the lower part of the home screen 6 2 4 15 About...

Page 31: ...the catch on the bottom of the unit with a at screwdriver and then tipping the cover outwards see illus 2 Once the front cover has been detached the two screws holding the back cover in place can be...

Page 32: ...out 24V out N C GND Illustration 5 Connecting Modbus via the RJ12 6P4C port Connect the Modbus cable to the Modbus port for a hand terminal on the PI Air2 Master and to the corresponding screw termina...

Page 33: ...and maintenance The PI HMI touch panel is maintenance free Please contact us if you have any further queries J Pichler Gesellschaft m b H 9021 KLAGENFURT Karlweg 5 Postfach 32 T 43 0 463 32769 The ven...

Page 34: ...complete with any optional acces sories and that all parts have been delivered in defect free condition N B In the event of any trans port damage and or missing parts this must be reported to the forw...

Page 35: ...ble collection centres and in compliance with the waste electrical and electronic equipment ordinance WEEE which pro vides for rati cation of community law directive 202 95 EC RoHS and the di rective...

Page 36: ...e case of line routes outside of the thermally insulated building shell these routes have to be sufficiently insulated in the cold area To ensure proper and functional system operation suitable insula...

Page 37: ...guarantee fault free function of the con densate discharge 10 2 1 Setting up the ventilation unit free standing installation When mounting the ventilation unit on a wall screw the four rubber buffers...

Page 38: ...e tank should be lled with sufficient water to test the reliable drainage of water and the leak tightness of all connections before commissioning Upon completion of the work all tools and installation...

Page 39: ...and secured against being switched back on Electrical connection and work on electri cal components may only be carried out by authorised electricians only The relevant national and local regula tion...

Page 40: ...7 5 2 9 When installing the control unit sepa rately a standard telephone cable or appropriately designed Modbus cable up to a max length of 50 m can be used We recommend the use of an AWG28 6C ribbon...

Page 41: ...d by a skilled instal ler Incorrect settings can lead to errors in the device 10 4 INITIAL STARTUP Basic procedure for initial startup Checking prior to initial startup Are all air lines and integrate...

Page 42: ...rical work observe the Safety instructions under Point 3 2 and in particular Point 3 2 3 for Electrical connection work 11 1 SAFETY DIRECTIONS For all questions pertaining to the sup plied Compact ven...

Page 43: ...killed personnel only If defects are discovered during the course of maintenance work these must be immediately recti ed to ensure a safe system operation Only genuine spare parts may be used for repl...

Page 44: ...o the electrical connecting cable to the motor It must not incur any damage A soft brush has to be used to clean the fan blades The fan housing is cleaned with a vacuum cleaner Damage to the rotating...

Page 45: ...tures we recommend at least an annual cleaning of the conden sate discharge the discharge line and the drain trap siphon For reliable operation of the system fault free functioning of the condensate d...

Page 46: ...rpose of documenting the service work this table has to be lled in after performance of any work on the system 11 4 6 Service table System installed by Date Item Service work e g lter change Performed...

Page 47: ...technical improvements to and optimize our products and reserve the right to change the design of the units or the technical speci cations without prior notice Designation Item number Control unit PI...

Page 48: ...H ZKLFK SURYLGHV IRU UDWLILFDWLRQ RI FRPPXQLW ODZ GLUHFWLYH 5R 6 DQG WKH GLUHFWLYH WKH GLUHFWLYH W 0otor Dnd GULYH YDULDEOH VSHHG 9HQWLODWLRQ FRQWURO 75 ORFDO GHPDQG FRQWURO T9G 3 T9Q SW8 TYL T9Q TYH...

Page 49: ...ZKLFK SURYLGHV IRU UDWLILFDWLRQ RI FRPPXQLW ODZ GLUHFWLYH 5R 6 DQG WKH GLUHFWLYH WKH GLUHFWLYH W 0otor Dnd GULYH YDULDEOH VSHHG 9HQWLODWLRQ FRQWURO 75 ORFDO GHPDQG FRQWURO T9G 3 T9Q SW8 TYL T9Q TYH T...

Page 50: ...approximation of the laws of the Member States establishing a framework for the setting of ecodesign requirements for energy related products Die Konformit t mit den Richtlinien wird nachgewiesen durc...

Page 51: ...OPERATING AND INSTALLATION INSTRUCTIONS SYSTEM VENTECH LG 500 P PAGE 51 Notes...

Page 52: ...KLAGENFURT AM W RTHERSEE Karlweg 5 T 43 0 463 32769 F 43 0 463 37548 STERREICH 1100 WIEN Doerenkampgasse 5 T 43 0 1 6880988 F 43 0 1 6880988 13 Sales offices in Slovenia and Serbia Sales partners in G...

Reviews: