9. Press the button „Transfer“ to start communication with the terminal. Your project is
about to be transferred.
The WinCC flexible software is now able to communicate with your operator panel.
5.3.6 ProTool/Pro v6.0 SP2
Please be sure that the interface configuration is correct as described in PD/PC-set
interface
1. Start ProTool/Pro by using the desktop link or program entry in the start menu.
2. Choose from the menu „File“ the sub menu „New“ or click on the right symbol.
3. The next dialog askes you which operator panel
you are using.
Mark the used panel (e.g. „TP 170A“)
4. „Next“ leads you to a new dialog. Type in the
specfic fields the name of the PLC device and
choose the used PLC in the driver selection (e.g.
„SIMATIC S7 – 300/400 V6.0“).
5. Via „Parameter...“ you are calling an
configuration dialog from the chosen PLC driver
Set up the station address of the panel (example
„1“) and of the PLC (example „2“).
Leave the point "Interface" in the standard
Page 35 of 92
Handbook MPI-II