6.1 Diagnostics by the LEDs
The LEDs indicate the status and error of the I1AM02 module by colours and blinking:
LED
Status of the I1AM
left
right
ready and power stage is
activated
green
green
ready and power stage is
NOT activated
green
off
motor is running
orange
green
module is not addressed
green
blinking red slowly (about 2 Hz)
no power supply available
on the 5 V bus
off
off
Initiator or SFI error
green
blinking red fast (about 5 Hz)