Manual MCC-1
MA 1249-A009 EN
40
Inputs
The inputs are connected to a common ground connection.
Input level: 24 V
DC
The input circuit protective resistor R
V
of
3.3 k
corresponds to 7 mA nominal driver
current at 24 V
DC
.
Signal level Low: < 0.4 V
DC
Signal level High: 20
– 30 V
DC
Fig. 31: Input circuit diagram
Outputs
The overload-safe outputs are equipped with protective diodes to protect the internal
circuitry. In the case of inductive loads (e.g. relay) each output should be additionally wired
with a protective diode mounted near the load in order to avoid EMC problems.
Max. 1 A current each output
Up to 3 A for all outputs
Fig. 32: Output wiring example