background image

5

www.UsePhoenix.com • [email protected]

Toll-Free 1-800-533-7533

passes through a filter/drier and capillary tubing which cause 

the refrigerant pressure and temperature to drop. It next 

enters the evaporator coil where it absorbs heat from the 

incoming air and evaporates.
The evaporator operates in a flooded condition, which means 

that all the evaporator tubes contain liquid refrigerant during 

normal operation. A flooded evaporator should maintain 

constant pressure and temperature across the entire coil, 

from inlet to outlet.
The mixture of gas and liquid refrigerant enter the 

accumulator after leaving the evaporator coil. The 

accumulator prevents any liquid refrigerant from reaching the 

compressor. The compressor evacuates the cool refrigerant 

gas from the accumulator and compresses it to a high 

pressure and temperature to repeat the process.

5.2 Troubleshooting

No dehumidification, neither hour meter display nor 

compressor run and POWER button does not turn ON.

1.   Unit unplugged or no power to outlet
2.   Defective control board
3.   Loose connection in internal wiring

No dehumidification, neither hour meter display nor 

compressor run with POWER button ON.

1.   Defective control board
2.   Loose connection in internal wiring

Some dehumidification, air mover runs continuously but 

compressor only runs sporadically.

1.   Unit is in defrost cycle, DEFROST light on
2.   Defrost thermistor defective or loose
3.   Loose connection in compressor circuit

4.   Defective compressor overload
5.   Defective compressor
6.   Defective relay
7.   Upper housing is not sealed to lower housing

No dehumidification, air mover runs but compressor does 

not.

1.   Bad connection in compressor circuit
2.   Safety float switch closed, check pump reservoir
3.   Defective compressor capacitor
4.   Defective compressor overload
5.   Defective compressor
6.   Defective control board

Air mover does not run. Compressor runs briefly but cycles 

on and off.

1.   Loose connection in blower circuit
2.   Obstruction prevents impeller rotation
3.   Defective air mover

Unit removes some water but not as much as expected.

1.   Air temperature and/or humidity have dropped
2.   Humidity meter and/or thermometer used are out of 

calibration

3.   Unit has entered defrost cycle
4.   Air filter dirty
5.   Defective defrost thermistor
6.   Low refrigerant charge
7.   Air leak such as loose cover
8.   Defective compressor
9.   Restrictive exhaust or inlet ducting

Unit runs but does not pump water.

1.   Hose kinked or plugged
2.   Pump motor defective
3.   Pump check valve plugged
4.   Bad connection in pump circuit
5.   Hose disconnected internally
6.   Defective control board (pump phase)

Unit pumps water automatically but not when PURGE button 

is pushed.

1.   Bad connection in PURGE button circuit
2.   Defective control board

Figure 7: Refrigeration system

Summary of Contents for R250

Page 1: ... Filter A 12 x12 x1 MERV 11 filter is standard Stacking Nesting Reduces space for ease of stacking and storage Patented ByPass Technology Increased performance over a wide temperature range Specifications subject to change without notice TS 889 08 15 4201 Lien Rd Madison WI 53704 Phoenix R250 Part No 4034460 Patent 7 246 503 D570 988 8 069 681 The Phoenix R250 has been redesigned from the inside o...

Page 2: ...at Warranty Five years 1st year 100 of Parts and Labor 2nd 5th year 100 of sealed refrigeration system parts Dimensions Unit Shipping Width 20 21 Height 33 5 35 25 Depth 20 21 Weight 109 lbs 125 lbs Patent 7 246 503 D570 988 8 069 681 3 Operation Place dehumidifier inside structure place condensate hose into a drain or a large water tight container and turn on To decrease drying times make sure al...

Page 3: ...ng the spiral wire under the four tabs Tape the duct to the top cover for a complete seal 3 6 Defrost Cycle If the low side refrigerant temperature drops below the defrost set point due to excessive frost formation on the evaporator coil the thermistor activates the solid state control and the defrost light The control cycles the compressor off and on by the thermistor temperature measurement The ...

Page 4: ...uld become clogged and require disassembly to clean 4 2 Storage There are two issues to consider when the Phoenix R250 is stored between uses and both pertain to the water trapped in the unit damage caused by freezing or biological growth The effect of the trapped water can be greatly reduced if precautions are taken to remove as much as possible before storage 1 Use the pump PURGE button to reduc...

Page 5: ...ontinuously but compressor only runs sporadically 1 Unit is in defrost cycle DEFROST light on 2 Defrost thermistor defective or loose 3 Loose connection in compressor circuit 4 Defective compressor overload 5 Defective compressor 6 Defective relay 7 Upper housing is not sealed to lower housing No dehumidification air mover runs but compressor does not 1 Bad connection in compressor circuit 2 Safet...

Page 6: ... Reassemble thermistor and dehumidifier using the above procedure in reverse Figure 10 Picture of the float safety switch 5 5 Condensate Pump The internal condensate pump removes water that collects in the reservoir To replace the condensate pump 1 Unplug the unit 2 Remove the front housing 3 Unplug the pump wires from the wire harness 4 Remove the condensate hose and the one screw attaching the p...

Page 7: ...BLK 3 YEL 7 E1 E3 E2 E5 E4 BLK 5 BRN 6 BLK 12 BLU 18 BLK 4 WHT S R C 4026354 C Figure 11 Wiring diagram 7 www UsePhoenix com sales UsePhoenix com Toll Free 1 800 533 7533 6 Options Accessories 4024750 Inlet Flex Duct 12 x 25 Metallize Polyester 4024935 Lay Flat Duct 10 Round x 250 Roll To order contact Therma Stor LLC at 1 800 533 7533 7 Wiring Diagram ...

Page 8: ...ord 1 4032315 14 Control Board 1 4026763 15 Capacitor Compressor 50 μF 1 4033032 06 16 Capacitor Impeller 15 μF 1 4033031 07 17 Thermistor 1 4031279 18 Handle lever 1 4026350 Description Qty Part No Compressor 1 4035407 Evaporator Coil 1 4033995 02 Condenser Coil 1 4033996 Condensate Pump 1 4034582 01 Float Safety Switch 1 4034374 Description Qty Part No Impeller Air Mover 1 4026657 Exhaust Grill ...

Page 9: ...The end user is responsible for normal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts of nature or any other cause beyond Therma Stor LLC s reasonable control Limitation and Exclusions If any Phoenix R250 Dehumidifier part is repaired...

Reviews: