5.2 Troubleshooting

No dehumidification, neither hour meter display nor  

 

       compressor run and POWER button does not turn ON.

1.   Unit unplugged or no power to outlet
2.   Defective control board
3.   Loose connection in internal wiring

No dehumidification, neither hour meter display nor 

compressor run with POWER button ON.

1.   Defective control board
2.   Loose connection in internal wiring

Some dehumidification, air mover runs continuously but 

compressor only runs sporadically.

1.   Unit is in defrost cycle, DEFROST light on
2.   Defrost thermistor defective or loose
3.   Loose connection in compressor circuit
4.   Defective compressor overload
5.   Defective compressor
6.   Defective relay
7.   Upper housing is not sealed to lower housing

No dehumidification, air mover runs but compressor does 

not.

1.   Bad connection in compressor circuit
2.   Safety float switch closed, check pump reservoir
3.   Defective compressor capacitor
4.   Defective compressor overload
5.   Defective compressor
6.   Defective control board

Air mover does not run. Compressor runs briefly but cycles 

on and off.

1.   Loose connection in blower circuit
2.   Obstruction prevents impeller rotation
3.   Defective air mover

Unit removes some water but not as much as expected.

1.   Air temperature and/or humidity have dropped
2.   Humidity meter and/or thermometer used are out of 

calibration

3.   Unit has entered defrost cycle
4.   Air filter dirty
5.   Defective defrost thermistor
6.   Low refrigerant charge
7.   Defective compressor
8.   Restrictive exhaust ducting

Unit runs but does not pump water.

1.   Hose kinked or plugged
2.   Pump motor defective
3.   Pump check valve plugged
4.   Bad connection in pump circuit
5.   Hose disconnected internally

Unit pumps water automatically but not when PURGE button 

is pushed.

1.   Bad connection in PURGE button circuit
2.   Defective control board

Evaporator coil frosted continuously, low dehumidifying 

capacity.

1.   Defrost thermistor loose or defective
2.   Low refrigerant charge
3.   Dirty air filter or restricted air flow
4.   Front housing is not sealed to rear housing

Compressor runs with POWER button OFF.

1.   Defective relay
2.   Defective control board

Summary of Contents for R150

Page 1: ... drying Energy Efficiency Removes 75 pints at AHAM while drawing only 5 5 amps Patented Bypass Technology Extends operating range to 110 F 150 CFM Optimized process air speeds drying and provides static pressures for ducting More Grain Depression Drier air from an LGR gets your jobs done quicker Focused Airflow Patented Focused outlet directs air downward across the wet surface Outlet Ducting 10 e...

Page 2: ...uct Options Outlet 10 Lay Flat Warranty Five years 1st year 100 of Parts and Labor 2nd 5th year 100 of Parts of sealed refrigeration system Size 30 high x 20 wide x 17 deep Weight 82 lbs Patent 7 246 503 7 281 389 7 540 166 3 Operation Place dehumidifier inside structure place condensate hose into a drain or a very large container and turn on To decrease drying times make sure all windows and door...

Page 3: ...ll continue to run causing air to flow through the evaporator coil and melt the ice when the compressor is off When the air temperature and or humidity increases the evaporator temperature will rise and the thermistor will end the defrost cycle at the temperature set point 3 6 POWER Button Press the POWER button to turn the dehumidifier on or off When starting the dehumidifier the display will sho...

Page 4: ...o that it drains into the heat exchanger 4 Use PURGE button to remove chemicals in reservoir Run PURGE until hose runs dry 5 Walk out hose to drain completely 6 Replace air filter 5 Service WARNING Servicing the Phoenix R150 with its high pressure refrigerant system and high voltage circuitry presents a health hazard which could result in death serious bodily injury and or property damage Only qua...

Page 5: ... compressor overload 5 Defective compressor 6 Defective control board Air mover does not run Compressor runs briefly but cycles on and off 1 Loose connection in blower circuit 2 Obstruction prevents impeller rotation 3 Defective air mover Unit removes some water but not as much as expected 1 Air temperature and or humidity have dropped 2 Humidity meter and or thermometer used are out of calibratio...

Page 6: ...place the pump hose wiring bolts and housing in the reverse order 6 Options Accessories 4026315 Air Filter Pleated 12 x 12 x 1 MERV 8 4025568 Air Filter Pleated 12 x 12 x 1 MERV 11 4024935 Lay Flat Duct 10 Round x 250 Roll To order contact Therma Stor LLC at 1 800 533 7533 5 3 Air Mover The motorized impeller has a PSC motor and internal thermal overload protection If defective the complete assemb...

Page 7: ...2 BLK 16 WHT 2 WHT 7 BLK 3 GRN BLU 8 BLK 4 BLK 11 YEL YEL BLU YEL YEL 10 RED 9 WHT 7 BLK GRY WHT 6 CONTROL BOARD RUN CAP FAN MOTOR PUMP SAFETY NO NC FLOAT WHT PUMP FAN LEVEL SWITCH THERMISTOR 1 LINE 2 NEUT 3 COMP RUN CAP PLUG 5 4 C R S COMPRESSOR BLK 15 BLK P N 4031273 REV C Wiring diagram 7 Wiring Diagram ...

Page 8: ... 1 4030483 9 Thermistor Probe 1 4034716 02 10 Capacitor Impeller 6 0 μF 1 4033031 03 11 Hex Bolts 1 4 20 x 1 25 6 1154012 12 Handle Bar 1 4031267 13 Handle Grip 1 4031268 14 Wheel 12 Black 2 4026851 15 Cotter Pin 2 1284404 16 Hub Cap Wheel Black 2 4027138 17 Handle Knob Lanyard 2 4033372 18 Control Board 1 4034457 19 Power Cord 1 4032297 Items listed are not shown Description Qty Part No Hose 1 4 ...

Page 9: ...The end user is responsible for normal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts of nature or any other cause beyond Therma Stor LLC s reasonable control Limitation and Exclusions If any Phoenix R150 Dehumidifier part is repaired...

Reviews: