background image

5

www.UsePhoenix.com • [email protected]

Toll-Free 1-800-533-7533

4.2 Troubleshooting

No dehumidification, neither blower nor compressor run 
and power switch does not light when ON.

1.   Unit unplugged or no power to outlet.
2.   Power switch defective.
3.   Loose connection in internal wiring.

No dehumidification, neither blower nor compressor run 
with power switch ON and lit.

1.   Low pressure control open.
2.   Power switch defective.
3.   Loose connection in internal wiring.
4.  Check thermostat setting.

Some dehumidification, blower runs continuously but 
compressor only runs sporadically.

1.   Unit is in defrost cycle.
2.   Defrost thermostat defective or loose.
3.   Loose connection in compressor circuit.
4.   Defective compressor overload.
5.   Defective compressor.
6.   Defective relay.

No dehumidification, blower runs but compressor does not.

1.   Bad connection in compressor circuit.
2.   Pump safety switch closed.
3.   Defective compressor capacitor.
4.   Defective compressor overload.
5.   Defective compressor.
6.   Defective relay.

Blower does not run. Compressor runs briefly but cycles on 
and off.

1.   Loose connection in blower circuit.
2.   Obstruction prevents impeller rotation.
3.   Defective blower.

Figure 5: Refrigeration system

Unit removes some water but not as much as expected.

1.   Air temperature and/or humidity have dropped.
2.   Humidity meter and/or thermometer used are out of 

calibration.

3.   Unit has entered defrost cycle.
4.   Air filter dirty.
5.   Defrost timer incorrectly set for conditions.
6.   Defective defrost thermostat.
7.   Low refrigerant charge.
8.   Air leak such as loose cover.
9.   Defective compressor.
10. Restrictive exhaust ducting.

Unit runs but does not pump water.

1.   Hose kinked or plugged.
2.   Pump motor or float switch defective.
3.   Pump check valve plugged.
4.   Bad connection in pump circuit.
5.   Hose disconnected internally.

Unit pumps water automatically but not when purge switch 
is pushed.

1.   Bad connection in purge switch circuit.
2.   Defective purge switch.

Evaporator coil frosted continuously, low dehumidifying 
capacity.

1.   Defrost thermostat loose or defective.
2.   Defrost timer incorrectly set or defective.
3.   Low refrigerant charge.
4.   Dirty air filter or air flow restricted.

Compressor runs with power switch OFF.

1.   Defective relay.
2.   Defective power switch.

 
4.3 Blower Replacement

The motorized impeller has a PSC motor and internal 
thermal overload protection. If defective, the complete 
assembly must be replaced.
1.   Unplug the power cord.
2.   Remove the top and cabinet front (6 screws).
3.   Disconnect the impeller leads.
4.   Remove four screws holding the impeller to the 

impeller brackets.

5.   Remove impeller. Use care to avoid hooking wiring, 

tubing or electrical components.

6.   Reassemble with the new impeller in the above 

procedure reversed.

Summary of Contents for Phoenix Arctic Max

Page 1: ...rs When used in conjunction with the Phoenix Solution LGR performance amplifier the Phoenix Arctic Max provides a reliable cooling air stream to maximize overall performance The Phoenix Arctic Max fea...

Page 2: ...ns carefully before using this unit Proper adherence to these instructions is essential to obtain maximum benefit from your Phoenix Arctic Max dehumidifier It is designed to be used INDOORS ONLY If us...

Page 3: ...ctic Max plugs into a common grounded outlet on a 15 Amp circuit It draws 11 8 Amps at 95 F 60 RH If used in a wet area a ground fault interrupter GFI is required If an extension cord is required it m...

Page 4: ...ly If the unit will not be exposed to freezing temperatures an alternative to reduce biological growth is to flush the unit with a bio fungicide that is approved for use with copper aluminum and polye...

Page 5: ...perature and or humidity have dropped 2 Humidity meter and or thermometer used are out of calibration 3 Unit has entered defrost cycle 4 Air filter dirty 5 Defrost timer incorrectly set for conditions...

Page 6: ...avity Drain Option If the condensate pump fails and cannot be replaced immediately the Phoenix Arctic Max can be used by draining by gravity 1 Unplug the unit and remove the front cover 2 Push the pla...

Page 7: ...r LLC PO BOX 8680 MADISON WI 53708 CAP YEL RED WHT WHT WHT BLU COMPRESSOR COMP BLK BLOWER CONTROL BLK BLK 5 3 2 MOTOR DEFROST 1 TIMER MOTOR SWITCH TIMER WHT VIO 1 DEFROST TIMER CONTROL THERMOSTAT BLK...

Page 8: ...Pump 1 4034495 16 10 Wire Duct Collar Cooling 1 4024078 17 Top 1 4029267 18 Handle Assembly 1 4026094 19 Pump Purge Switch 1 4021796 20 Hour Meter 1 4028795 21 Power Switch 1 4021822 22 Skid Plate 1 4...

Page 9: ...is warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident...

Reviews: