2.10  Low Pressure Control

If the low side refrigerant pressure drops to 15 PSIG, the 
low pressure control opens and shuts off the compressor 
and blower. It is an automatically reset control. Its primary 
function is to prevent damage to the compressor if a leak 
develops in the refrigeration system. It may also open if 
the unit is A) used in a cool area (below 50°F) and the 
defrost timer is not adjusted or B) stored where it is below 
40°F and then started. Under these conditions, the unit 
will restart within several minutes; it may cycle several 
times until the unit warms up.

3 Maintenance

3.1 Air Filter

The Phoenix Arctic Max is equipped with 2 pleated fabric 
air filters that must be checked regularly. The cooling air 
flow filter is a MERV-11 high efficiency filter. The condener 
exhaust filter is a MERV-7. Operating the unit with a dirty 
filter will reduce the dehumidifier’s capacity and efficiency 
and may cause the compressor to cycle off and on 
unnecessarily on the defrost control.
The filter can generally be vacuumed clean several times 
before needing replacement. Replacement filters can be 
ordered from the factory or purchased locally if available.

WARNING: DO NOT operate the unit without the filter or 
with a less effective filter as the heat exchange coils inside 
the unit could become clogged and require disassembly to 
clean.

3.2 Storage

There are two issues to consider when the Phoenix Arctic 
Max is stored between uses and both pertain to the 
water trapped in the unit: damage caused by freezing or 
biological growth.
The effect of the trapped water can be greatly reduced 
if precautions are taken to remove as much as possible 
before storage.
1.   Use the pump purge switch to reduce the water level 

in the reservoir.

2.   Stretch the hose flat to drain it completely.

If the unit will not be exposed to freezing temperatures, an 
alternative to reduce biological growth is to flush the unit 
with a bio-fungicide that is approved for use with copper, 
aluminum and polyethylene. To flush:
1.   Run the hose to a drain.
2.   Remove the air filter. Remove top and front cover.

Slowly pour a quart of the chemical through the 
evaporator coil fins and drain into the drain pan.

3.  Flush coil with water.
4.   Hold in the pump purge switch to reduce the water 

level in the reservoir.

4 Service

WARNING: Servicing the Phoenix Arctic Max with its high 
pressure refrigerant system and high voltage circuitry 
presents a health hazard which could result in death, 
serious bodily injury, and/or property damage. Only 
qualified service people should service this unit. 
Do not operate unit without the front panel in place.

4.1 Technical Description

The Phoenix Arctic Max uses a refrigeration system similar 
to an air conditioner’s to remove heat and moisture from 
incoming air and to add heat to the air that is discharged.
Hot, high pressure refrigerant gas is routed from the 
compressor to the condenser coil. The refrigerant is cooled 
and condensed by giving up its heat to the air that is about 
to be discharged from the unit. The refrigerant liquid then 
passes through a filter/drier and capillary tubing which 
cause the refrigerant pressure and temperature to drop. It 
next enters the evaporator coil where it absorbs heat from 
the incoming air and evaporates.
The evaporator operates in a flooded condition, which 
means that all the evaporator tubes contain liquid 
refrigerant during normal operation. A flooded evaporator 
should maintain constant pressure and temperature 
across the entire coil, from inlet to outlet.
The mixture of gas and liquid refrigerant enter the 
accumulator after leaving the evaporator coil. The 
accumulator prevents any liquid refrigerant from reaching 
the compressor. The compressor evacuates the cool 
refrigerant gas from the accumulator and compresses it to 
a high pressure and temperature to repeat the process.

Summary of Contents for Phoenix Arctic Max

Page 1: ...rs When used in conjunction with the Phoenix Solution LGR performance amplifier the Phoenix Arctic Max provides a reliable cooling air stream to maximize overall performance The Phoenix Arctic Max fea...

Page 2: ...ns carefully before using this unit Proper adherence to these instructions is essential to obtain maximum benefit from your Phoenix Arctic Max dehumidifier It is designed to be used INDOORS ONLY If us...

Page 3: ...ctic Max plugs into a common grounded outlet on a 15 Amp circuit It draws 11 8 Amps at 95 F 60 RH If used in a wet area a ground fault interrupter GFI is required If an extension cord is required it m...

Page 4: ...ly If the unit will not be exposed to freezing temperatures an alternative to reduce biological growth is to flush the unit with a bio fungicide that is approved for use with copper aluminum and polye...

Page 5: ...perature and or humidity have dropped 2 Humidity meter and or thermometer used are out of calibration 3 Unit has entered defrost cycle 4 Air filter dirty 5 Defrost timer incorrectly set for conditions...

Page 6: ...avity Drain Option If the condensate pump fails and cannot be replaced immediately the Phoenix Arctic Max can be used by draining by gravity 1 Unplug the unit and remove the front cover 2 Push the pla...

Page 7: ...r LLC PO BOX 8680 MADISON WI 53708 CAP YEL RED WHT WHT WHT BLU COMPRESSOR COMP BLK BLOWER CONTROL BLK BLK 5 3 2 MOTOR DEFROST 1 TIMER MOTOR SWITCH TIMER WHT VIO 1 DEFROST TIMER CONTROL THERMOSTAT BLK...

Page 8: ...Pump 1 4034495 16 10 Wire Duct Collar Cooling 1 4024078 17 Top 1 4029267 18 Handle Assembly 1 4026094 19 Pump Purge Switch 1 4021796 20 Hour Meter 1 4028795 21 Power Switch 1 4021822 22 Skid Plate 1 4...

Page 9: ...is warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident...

Reviews: