background image

4

USEPHOENIX.COM

1.800.533.7533

connecting to two-slot receptacles. The green grounding 

lug extending from the adapter must be connected to a 

permanent ground such as a properly grounded outlet box. 

The adapter should not be used if a three-slot grounded 

receptacle is available.

2.3 Ducting

The Phoenix FireBIRD Compact 20 can be ducted at the 

inlet, the outlet or both. The FireBIRD Compact 20 inlet and 

outlet duct are designed to accommodate 8” flexible duct. 

When selecting flexible ducting keep in mind anticipated 

outlet temperatures. Air temperature increase is typically 50 

to 80 degrees F. Adding ducting decreases airflow which can 

increase outlet temperatures by up to 40 additional  

degrees F. 
 

NOTE: It is strongly discouraged to use mylar ducting as this 

could burn and cause a fire. 

2.4 Control Panel

Fan Mode Switch: This switch allows the user to operate in 

‘FAN ON’ or ‘FAN AUTO’ mode. In ‘FAN ON’ mode, the blower 

will remain on whenever the unit is energized. This mode 

is recommended for normal operation where constant 

air circulation is desired. In ‘FAN AUTO’ mode, the blower 

will only energize when there is a demand for heat from 

the remote thermostat connection. To use this mode, the 

CONTROL POWER switch must be set to ‘THERMOSTAT 

CONTROLLED.’ This mode is recommended for applications 

that do not require constant air circulation during heating. 

 

Control Power Switch: The CONTROL POWER switch can be 

used to turn the unit ON, OFF, or set the unit to be controlled 

by an external thermostat. In ‘ALWAYS ON’ mode, the 

Compact 20 uses an internal thermostat preset at 140F. 

Heat will continue to be produced until the air flowing into 

the inlet reaches 140F. At this point, internal safeties will 

turn off the heating elements until the inlet air temperature 

reaches 130F. In ‘THERMOSTAT CONTROLLED’ mode, the 

Compact 20 looks for a closed circuit at the THERMOSTAT 

connection on the front of the control panel. Any dry contact 

switch or the included remote thermostat with 25’ of wire 

can perform this function.

Start/Reset Switch: The START/RESET Switch is used to 

enable the Compact 20 to produce heat. If at any time 

power to the control circuit is lost or if a fault condition 

occurs, the Compact 20 will go into the FAULT/NOT 

RUNNING mode. Pushing the START/RESET switch will 

energize the control circuit and restart the Compact 20.

OK/Running Lamp: The OK/RUNNING lamp will illuminate 

when the control circuit is energized. If the lamp is lit, the 

Compact 20 is under the control of either the internal or 

external thermostat (depending on which thermostat is 

selected with the control power switch). In this state, the 

heater will be on until it reaches cycling temperatures 

(130F-140F) and will then self-regulate at this range. 

FAULT/NOT RUNNING Lamp: If the FAULT/NOT RUNNING 

lamp is lit, the contactor control circuit is not energized, 

which will disable the heater circuits and no heat will be 

produced.

Hour Meter: The digital hour meter measures the cumulative 

time that the unit is turned on to tenths of an hour. It stores 

and displays the total when the unit is unplugged. It resets 

to zero after 99,999.9 hours of operation.

Heat ON/OFF Switches: These switches individually 

control the heating elements. Each switch connects and 

disconnects the power from the receptacle next to it. These 

switches are lighted to indicate when power is connected 

and the corresponding heating element is on.

Remote Thermostat Connection: There are two spring 

loaded terminals for connecting the thermostat wiring on 

the control panel. Connect one wire to each terminal. For 

applications where the FireBIRD Compact 20 is placed 

outside the space to be heated (e.g. ducting heat into a 

chamber), the 25’ cord allows you to place the thermostat 

inside the heated space. 

  

  

  

Grounding Pin

Plug

Adapter

Outlet

Grounding 

Means

Metal 

Screw

Summary of Contents for FireBIRD Compact 20

Page 1: ... by ETL to UL Safety Standards 15 Amp Operation at 120VAC up to 4 independent circuits 20 000 Btu Remote Thermostat with 25 connecting wire included with unit Standard MERV 11 air filter included Multiple ducting options 8 Outlet Duct 8 Inlet Duct Optional Stainless Steel Cabinet Double Walled Screened Enclosure for heating elements Automatic Internal 140 F Safety Thermal Cutout Stackable for easy...

Page 2: ...ELECTRIC SHOCK or FIRE or damage the heater To prevent a possible fire do not block air intakes or exhaust in any manner Do not use on soft surfaces such as a bed where openings may become blocked Device has hot and arcing or sparking parts inside Do not use in areas where gasoline paint or flammable liquids are used or stored Use device only as described in this manual Any other use not recommend...

Page 3: ...que façon que ce soit Évitez d utiliser sur les surfaces souples telles un lit où les entrées risquent d être bloquées L appareil comporte des pièces chaudes pouvant produire des arcs électriques étincelles Ne pas utiliser là où de l essence de la peinture et des liquides inflammables sont utilisés ou entreposés Utilisez cet appareil uniquement aux fins décrites dans le manuel Toute utilisation no...

Page 4: ... the Compact 20 looks for a closed circuit at the THERMOSTAT connection on the front of the control panel Any dry contact switch or the included remote thermostat with 25 of wire can perform this function Start Reset Switch The START RESET Switch is used to enable the Compact 20 to produce heat If at any time power to the control circuit is lost or if a fault condition occurs the Compact 20 will g...

Page 5: ...The heating elements are operated by contactors operated by a 24VAC control circuit For safety there are a set of thermal switches that will de energize the heating elements if the temperature in the element chamber rises to an unacceptable level caused by lack of airflow or high ambient temperature An additional safety switch limits the incoming air temperature to approximately 140F This switch s...

Page 6: ...T AIR TEMPERATURE THERMOSTAT A B RELAY R 3 RELAY R 1 RELAY R 2 A A B B 28 VAC TRANSFORMER HEATER SWITCH 1 HEATER SWITCH 2 PUSH TO START BLU G R N BRN BLK BLU G R N HOUR METER CAPACITOR MASTER POWER SWITCH CIRCUIT POWER SWITCH RELAY CONTACT R1B R2A R2B R1A 1250 WATT HEATER 1 28 VAC PRIMARY 1440 WATT HEATER 2 4 RELAY 3 COIL R3 AIR TEMPERATURE THERMOSTAT R1 R2 R3A R3B R3B RELAY 1 COIL RELAY 2 COIL RE...

Page 7: ...n Off Switches 3 4021822 7 External TSTAT Connector 1 4036122 8 Green Indicator Light 1 4034878 9 Red Indicator Light 1 4034886 Item Description QTY Part No 10 Blower 1 4032769 11 Thermostat 1 4030614 12 10mfd Capacitor 1 4033031 05 13 24VAC Transformer 1 4022487 14 Relay DPDT 3 4029575 15 Heater Element 1 4034885 16 Tinnerman Clip 10 4032761 17 Switch Fan Mode 1 4025560 9 1 2 3 4 5 6 7 8 10 11 12...

Page 8: ...tation and Exclusions If any Phoenix FireBIRD Compact 20 part is repaired or replaced the new part shall be warranted for only the remainder of the original warranty period applicable thereto but all warranty periods will be extended by the period of time if any that the Phoenix FireBIRD Compact 20 is out of service while awaiting covered warranty service UPON THE EXPIRATION OF THE WRITTEN WARRANT...

Reviews: