8 Trouble Shooting
9 Troubleshooting
Trouble
Probable Fault
Probable Cause
Corrective Action
1.
Main power off
Check main power and cable
2.
Main disconnect open
Close or replace disconnect
3.
Selector switch open
Close or replace switch
Unit Stopped
(fan off, no
heater)
Power/Control
Failure
4.
Dehumidistat
Repair or replace
1.
Motor circuit breaker or
overload tripped
Reset circuit breaker or
overload
2.
Contactor failure
Repair or replace
3.
Motor winding failure
Repair or replace
Fan off
(Rotor turns)
Power/Mechanical
Failure
4.
Fan motor failure
Repair or replace
1.
Excessive unconditioned make-
up air
Reduce make-up air
2.
Leaking ducts or air handling
equipment outside controlled
area
Seal leaks
3.
Access opening to area not
sealed
Close and seal
Excessive
infiltration of
humid air into the
controlled area
4.
Area not vapor tight
Seal with paint or vapor barrier
1.
Dehumidistat needs
adjustment
Re-adjust
2.
Improper settings
Re-adjust
Faulty humidity
controls
3.
Defective
Replace
1.
Dirty filter
Clean or replace
2.
Obstruction at inlet, outlet or
ducting
Remove obstruction
Inadequate air flow
3.
Clogged desiccant media
(high pressure differential
across media)
Remove and replace media
rotor
1.
Element failure
Check elements – repair or
replace
2.
Low / no voltage
Correct power supply /
breakers
Inadequate or no
reactivation heat
3.
Control elements failure
Control set point / repair or
replace
1.
Air leaking into dehumidifier
Replace access door gaskets
Air seals and
gaskets
2.
Air bypassing media or leaking
seals
Check media position, replace
seals
1.
Chain
Repair or replace
2.
Motor/gear box
Repair or replace
3.
Damaged desiccant rotor
Repair or replace
Unit running
but humidity
rises
Ineffective
desiccant media
4.
Contaminated or damaged
desiccant
Replace desiccant rotor