QUINT4-INV/24DC/1AC/600VA/USB
108987_en_00
PHOENIX CONTACT
9 / 25
Electromagnetic compatibility / Conformance with EMC Directive 2014/30/EU
Noise emission in accordance with EN
61000-6-4
Conducted noise emission
EN 61000-6-4
Noise emission
EN 61000-6-4
Immunity in accordance with EN
61000-6-2
CE basic standard
EN
61000-6-2 requirement
Tested
Electrostatic discharge EN 61000-4-2
Housing contact discharge
± 6 kV
± 6 kV
Housing air discharge
± 8 kV
± 8 kV
Comments
Criterion B
Criterion A
Electromagnetic HF field EN
61000-4-3
Frequency range
80 MHz ... 1 GHz
80 MHz ... 6 GHz
Test field strength
10 V/m
10 V/m
Comments
Criterion A
Criterion A
Fast transients (burst) EN
61000-4-4
Input
± 2 kV
± 2 kV
DC input
± 2 kV
± 2 kV
Output
± 2 kV
± 2 kV
Signal
± 2 kV
± 2 kV
Signal USB
--
± 2 kV
Comments
Criterion B
Criterion A (B for USB)
Surge voltage load (surge) EN
61000-4-5
Input
± 1 kV (symmetrical)
± 2 kV (asymmetrical)
± 1 kV (symmetrical)
± 2 kV (asymmetrical)
Output
± 1 kV (symmetrical)
± 2 kV (asymmetrical)
± 2 kV (symmetrical)
± 4 kV (asymmetrical)
Signal
1 kV (asymmetrical)
1 kV (asymmetrical)
Comments
Criterion B
Criterion A
Conducted interference EN 61000-4-6
Frequency range
0.15 MHz ... 80 MHz
0.15 MHz ... 80 MHz
Signal
10 V
10 V
Comments
Criterion A
Criterion A
Power frequency magnetic field EN 61000-4-8
Frequency
50 Hz , 60 Hz
50 Hz , 60 Hz
Signal
30 A/m
30 A/m
Comments
Criterion A
Criterion A
Key
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected by the device itself.