Phoenix Contact QUINT1AC Manual Download Page 21

QUINT4-INV/24DC/1AC/600VA/USB

108987_en_00

PHOENIX CONTACT

21 / 25

12.3.2 Application example: Operation on a battery

The inverter DC input voltage is supplied via a battery with 

24

 

V nominal voltage.

A battery has the property that the battery terminal voltage 

increases again at low voltage and the resulting load 

shedding (for protection against deep discharge). This 

increase can amount to several volts. Set the activation 

threshold correspondingly high.

Lower DC input voltage limit: 21

 

V

 

DC

Upper DC input voltage limit: 30

 

V

 

DC

Activation threshold: 27

 

V

 

DC

Figure 20

Application example: Operation on a battery

In this setting example, it is ensured that the inverter first 

switches on at a battery voltage of 27

 

V

 

DC and, for deep 

discharge protection, switches off at 21

 

V

 

DC.

13

Parallel operation

You can connect up to three inverters in parallel in order to 

increase the power or for redundant load supply. The 

settings are made via the rotary selector switches on the 

front of the device (see section: Setting the operating mode).

The device adopts the rotary selector switch settings when 

starting up. Changes to these settings during ongoing 

operation will not affect the function of the inverters.

In parallel operation, connect the individual inverters via the 

parallel running communication interfaces using RJ45 

twisted pair patch cables.

Connect the outputs of the inverters together directly. The 

output power is split symmetrically across the individual 

inverters in each parallel operating mode.

Observe the following points when carrying out parallel 

connection:

1.

Set the operating mode of the individual inverters via the 

rotary selector switches.

2.

Use the same cable cross sections for wiring.

3.

Use the same cable lengths up to the AC convergence 

point.

4.

Operate the inverters in the same temperature 

conditions.

5.

Comply with the national safety regulations. In 

particular, comply with the regulations on grounding the 

neutral conductor. In the delivery state, this is ensured 

through the pre-installed bridge in terminals 2.4 and 1.3.

During parallel operation, the following settings are 

transferred from the master device to the slave device. The 

settings of the slave device are ignored here:

Remote signal terminal operation

Settings via the POWER MANAGEMENT SUITE 

configuration software. Changes to the settings can 

only be made using the master device and are 

permanently transferred to the slave devices. 

Parameters can be read off from all devices.

The following alarm messages are available in parallel 

operation:

Parallel mode is not possible:

This combination of master or slave devices is 

impermissible.

No  redundancy:

The device fails in redundant operation or

the total power is too high in redundant operation. This 

means that in the case of a device fault, the load cannot 

be supplied using a device.

System error:

Each alarm in parallel operation is displayed as a sum 

message. All alarm signal outputs can be used.

13.1

Increasing power

Parallel connection for increased power is used when 

extending existing systems. If the individual inverter does 

not cover the current consumption of the most powerful 

load, parallel connection of inverters is recommended. The 

output power is doubled by using two inverters connected in 

parallel.

Information on the device settings is to be found in the 

section Setting the operating mode section.

13.2

Redundant operation

Redundant operation of inverters is suitable for supplying 

systems and system parts which place particularly high 

demands on operational safety.

In the event of a fault, it must be ensured that one of the 

individual inverters is able to provide the total required 

power for the load.

Information on the device settings is to be found in the 

section Setting the operating mode section.

13.3

3AC operation

3AC operation is suitable for supplying systems and system 

parts that require symmetrical 3-phase control.

Information on the device settings is to be found in the 

section Setting the operating mode section.

. . .

. . .

. . .

[V DC]

Device

on

off

21

27

30

29,5

Summary of Contents for QUINT1AC

Page 1: ...ased performance and redundancy 3 AC Integrated USB interface High efficiency Technical data short form Nominal input voltage 24 V DC Input voltage range 20 V DC 30 V DC Current consumption typ 23 A max 28 A Apparent power 600 VA Real power 480 W Nominal output voltage Nominal output current 100 load 120 V AC 5 A 100 V AC 6 A 130 V AC 4 6 A 230 V AC 2 6 A 200 V AC 3 A 240 V 2 5 A Output voltage to...

Page 2: ...mounting position 14 7 3 Mounting the inverter 14 7 4 Removing the inverter 15 7 5 Wall mounting 15 8 Device connection 17 8 1 Connection parameters 17 9 Device connection terminal blocks 17 9 1 DC input 17 9 2 AC output 18 9 3 Connection terminal block signaling 18 10 Interface 18 10 1 USB mini type B 18 11 Device operation 19 11 1 Setting the operating mode 19 11 2 Remote 19 11 3 Start 120 V Sta...

Page 3: ...C 600VA USB 108987_en_00 PHOENIX CONTACT 3 25 14 Signaling 22 14 1 LED indicators and signal outputs 23 14 2 Signal outputs 24 14 3 Signal inputs 24 15 Derating 25 15 1 Ambient temperature 25 15 2 Installation height 25 ...

Page 4: ...ed on the left right UWA 130 2901664 1 Universal wall adapter for securely mounting the device in the event of strong vibrations The device is screwed directly onto the mounting surface The universal wall adapter is attached on the top bottom UWA 182 52 2938235 1 Type 2 3 surge protection consisting of protective plug and base element with integrated status indicator and remote signaling for singl...

Page 5: ...t plastic sleeve 0 2 mm 4 mm Conductor cross section AWG kcmil 30 10 Stripping length 8 mm Tightening torque 0 5 Nm 0 6 Nm Output data Apparent power 600 VA Real power 480 W Power factor cos phi 0 8 Nominal output voltage Nominal output current 100 load 120 V AC 5 A 100 V AC 6 A 130 V AC 4 6 A 230 V AC 2 6 A 200 V AC 3 A 240 V 2 5 A Output voltage tolerance no soft start 2 Nominal output frequency...

Page 6: ...lexible with ferrule without plastic sleeve 0 2 mm 4 mm Conductor cross section AWG kcmil 30 10 Stripping length 8 mm Tightening torque 0 5 Nm 0 6 Nm Status and diagnostic indicator signal output Alarm Connection labeling 3 1 Switching output Transistor output active Output voltage 24 V Continuous load current 20 mA LED status indicator red Status and diagnostic indicator signal output AC OK Conne...

Page 7: ...stic indicator signal output Out 1 Connection labeling 3 5 Switching output Transistor output active Status and diagnostic indicator signal input Remote Connection labeling 3 8 Low signal Connection to SGnd with 2 7 kΩ High signal Open 35 kΩ between remote and SGnd Signal ground SGnd Connection labeling 3 9 Function Signal ground Reference potential For signal inputs and signal outputs Signal conn...

Page 8: ...egory according to EN 61010 2 201 II MTBF IEC 61709 SN 29500 532525 h 40 C Degree of protection Protection class IP20 I Dimensions W H D 180 130 125 mm Weight 2 5 kg Ambient conditions Ambient temperature operation 25 C 60 C Derating Output power 50 C 2 5 K Ambient temperature storage transport 40 C 85 C Humidity non condensing 95 Installation height 3000 m Derating Output power 2 000 m 0 6 100 m ...

Page 9: ...urst EN 61000 4 4 Input 2 kV 2 kV DC input 2 kV 2 kV Output 2 kV 2 kV Signal 2 kV 2 kV Signal USB 2 kV Comments Criterion B Criterion A B for USB Surge voltage load surge EN 61000 4 5 Input 1 kV symmetrical 2 kV asymmetrical 1 kV symmetrical 2 kV asymmetrical Output 1 kV symmetrical 2 kV asymmetrical 2 kV symmetrical 4 kV asymmetrical Signal 1 kV asymmetrical 1 kV asymmetrical Comments Criterion B...

Page 10: ...trol cabinet Keep flames embers or sparks away from the module Provide a switch circuit breaker close to the device at the DC input and the AC output respectively which are marked as the disconnecting device for this device This is the safety alert symbol It is used to alert you to potential personal injury hazards Obey all safety measures that follow this symbol to avoid possible personal injurie...

Page 11: ...re replace fuses only with those that have the same type and rating Relevant fuses can be found in the accessories in the ordering data The device is maintenance free Repairs may only be carried out by the manufacturer Opening the housing invalidates the warranty The inverter may only be used for its intended use Improper use invalidates the device protection Provide an easily reached switch fuse ...

Page 12: ...llel Port 5 2 DC OK 15 1 14 13 12 11 10 8 7 6 5 4 3 2 9 No Designation Connection labeling 1 PE N bridge connection terminal blocks 2 4 1 3 2 Universal DIN rail adapter rear of housing 3 Signaling connection terminal blocks 3 1 3 9 4 LED parallel run 5 Communication interface parallel run 5 2 6 Rotary selector switch parallel run mode Operating mode 7 LED status indicator Alarm 8 Rotary selector s...

Page 13: ... K 3 3 P P n 3 4 O u t 1 3 5 S ta rt 2 3 0 V 3 6 S ta rt 1 2 0 V 3 7 R e m o te 3 8 S G n d 3 9 L1 Slave L1 Master L1 Master Soft Start L3 L2 Single Redundancy Power 3AC Link Parallel Port 5 2 5 1 130 50 50 180 DC OK 125 132 5 C 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 9 2 1 2 2 2 3 1 1 1 2 5 1 5 2 Output AC N L PE Alarm AC OK DC OK P Pn Out 1 Start 230V Start 120V Remote SGnd Input DC Parallel PE N Port...

Page 14: ...n To ensure sufficient convection maintain an adequate minimum clearance between the inverter and above below the installed devices For information on the required minimum clearances refer to the section Device dimensions and keep out areas Alarm DCOK ACOK Out1 P Pn Start230V Start120V Remote SGnd 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 9 QUINT AC INV 600VA Alarm DC OK 3A C Link Po we r Sing le Re dunda...

Page 15: ...tremely high level of mechanical stability is ensured 7 5 1 Mounting the UWA 182 52 universal wall adapter Proceed as follows to disassemble the universal DIN rail adapter that comes pre mounted 1 Remove the screws for the universal DIN rail adapter using a suitable screwdriver Torx 10 2 Remove the universal DIN rail adapter from the rear of the device 3 Position the universal wall adapter in such...

Page 16: ...versal DIN rail adapter from the rear of the device 3 Position the two piece universal wall adapter on the right and left side of the housing 4 Insert the Torx screws into the appropriate hole pattern on the universal wall adapter so that the necessary mounting holes of the device can be accessed 5 Screw the two piece universal wall adapter onto the device Figure 9 Mounting the UWA 130 universal w...

Page 17: ...e output voltage supply system configuration mm 0 2 4 0 2 4 0 2 4 0 2 1 5 Input DC 1 1 1 2 Output AC 2 1 2 3 Signals 3 1 3 9 N 2 4 PE 1 3 Screw 0 2 6 0 2 6 0 2 6 0 2 1 5 mm 0 2 4 0 2 4 0 2 4 0 2 1 5 mm mm 0 2 4 0 2 4 0 2 4 0 2 1 5 Cu 30 10 30 10 30 10 30 12 8 8 8 8 L mm 0 5 0 6 0 5 0 6 0 5 0 6 0 5 0 6 Nm lb in 5 7 5 7 5 7 5 7 AWG Alarm DCOK ACOK Out1 P Pn Start230V Start120V Remote SGnd 3 1 3 2 3 ...

Page 18: ...ommunicating with a PC or a higher level controller Figure 14 Service USB interface Mini type B device bottom 5 1 Alarm DCOK ACOK Out1 P Pn Start230V Start120V Remote SGnd 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 9 QUINT AC INV 600VA Alarm 3A C Lin k Po we r Sin gle Re dundanc y AC OK P Pn Re mote L1 Slav e L1 L1 L2 L3 M aster M aster So ft Sta rt Pa rallel Po rt 5 2 L N 2 1 2 2 2 3 Outpu t AC 12 0 23 0V...

Page 19: ...ion L1 Slave 1st slave device in the mode 3AC switch position L2 2nd slave device in the mode 3AC switch position L3 Master device in the mode 3AC with inclined start characteristic curve switch position L1 Master Soft Start Only applicable in 3AC operation at 230 V output voltage In this switch position the output voltage drops briefly during startup Figure 17 Rotary selector switch parallel run ...

Page 20: ... or 240 V 50 Hz default or 60 Hz 12 3 Input voltage setting options You can set the following DC input voltage parameters via the POWER MANAGEMENT SUITE software Lower DC input voltage limit 20 V DC 26 5 V DC default 20 V DC Upper DC input voltage limit 28 V DC 30 V DC default 30 V DC Activation threshold 20 5 V DC 27 V DC default 23 V DC Note that the activation threshold must be at least 0 5 V h...

Page 21: ...ions on grounding the neutral conductor In the delivery state this is ensured through the pre installed bridge in terminals 2 4 and 1 3 During parallel operation the following settings are transferred from the master device to the slave device The settings of the slave device are ignored here Remote signal terminal operation Settings via the POWER MANAGEMENT SUITE configuration software Changes to...

Page 22: ... level control system Figure 21 LED indicators Alarm DCOK ACOK Out1 P Pn Start230V Start120V Remote SGnd 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 9 QUINT AC INV 600VA Alarm DC OK 3A C Link Po we r Sing le Re dundancy AC OK P Pn Re mote L1 Slav e L1 L1 L2 L3 M aster M aster So ft Start Pa rallel Po rt 5 2 L N 2 1 2 2 2 3 Outpu t AC 12 0 23 0V N 2 4 1 3 5 1 23 0V 12 0V 1 1 1 2 Inpu t DC 24 V AC OK P Pn Rem...

Page 23: ...h high high high low high low low low high low high low low low high low low low low high high high low active low Alarm AC OK high high P Pn Note Device start input voltage too low too high Initialization LED test 3 sec Device off Device start Device start alarm output off alarm Output off remote contact connected to SGnd alarm Output on overload Output on alarm Output on Device start input voltag...

Page 24: ... permanently depending on the detected voltage range You can assign other additional information to this signal output using the POWER MANAGEMENT SUITE software P Pn If the output power exceeds the maximum permitted output power the signal output is active high level The signal status can be inverted via the POWER MANAGEMENT SUITE software A digital transistor output is available as a signal conta...

Page 25: ...Figure 23 Temperature dependent derating 15 2 Installation height The inverter can be operated at an installation altitude of up to 2000 m without any limitations Different data applies for installation locations above 2000 m due to the differing air pressure and the reduced convection cooling associated with this A power derating of 0 6 100 m should be observed for installation heights between 20...

Reviews: