IL PB BK DI8 DO4/EF-PAC
B-2
PHOENIX CONTACT
7725_en_01
Bit 3 can be used in the context of dynamic configuration. If a new activation status is
specified via object 6 or 7, it is mandatory. If the connection to the PROFIBUS master is then
interrupted and if the original parameterization is transmitted by the master during restart,
the activation status is maintained. The dynamic configuration does not have to be executed
again.
However, if the activation status is reset during a restart, set bit 3 once following dynamic
configuration via index 6 or 7.
In this way, both options are available:
–
Restart with original configuration
–
Restart with last dynamic configuration
Bit = 0: Terminal and slot inactive
Bit = 1: Terminal and slot active
Index 5:
PCP status
Function:
Position and communication status of PCP terminal
Access:
Read
Length:
3 bytes per PCP terminal -> 48 bytes, maximum
Structure:
Byte 1: Position in the station (slot number)
Byte 2: Status of PCP connection
–
00
hex
No connection
–
01
hex
Connection OK
–
FF
hex
Error during connection establishment
Byte 3: Reserved
Index 6:
Terminal activation
Function:
Activation/deactivation of I/O terminals
Access:
Read and write
Length:
8 bytes
Structure:
See below
Byte 1
Byte 2
Bytes 3 ... 7
Byte 8
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
...
57
58
59
60
61
62
63
x
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0