IB IL 24 AI 2/SF-230
6232A
13
Figure 10
Process data output words
One process data output word is available for
the configuration of each channel.
Set bit 15 of the corresponding output word to 1
to configure the terminal. If bit 15 = 0 the preset
configuration is active.
Bit 15:
Bit 9 and bit 8:
Bit 5 and bit 4:
Bit 3 through bit 0:
MSB
Most significant bit
LSB
Least significant bit
C h a n n e l 1
M S B
L S B
0
1 4
1 3
1 2
1 1
1 0
9
8
7
6
5
4
3
2
1
C h a n n e l 2
5 5 6 4 0 0 0 6
F o r m a t
M e a s u r i n g r a n g e
P r o c e s s d a t a w o r d 1
P r o c e s s d a t a w o r d 2
1 5
F i l t e r
C o n f i g u r a t i o n
Code
Configuration
0
Default
1
Configuration data
Code
Filter
00
16-sample mean value (default)
01
Mean-value generation Off
10, 11
Reserved
Code
Format
00
IB IL (15 bits) (default)
01
IB ST (12 bits)
10
IB RT (15 bits)
11
Standardized display
Code
Measuring Range (Voltage)
0000
0 V through 10 V (default)
0001
±10 V
0010
through
0111
Reserved
Set all reserved bits to 0.
Code
Measuring Range (Current)
1000
0 mA through 20 mA
1001
±20 mA
1010
4 mA through 20 mA
1011 through
1111
Reserved