The process data formats "IB IL" and "Standardized display" support extended diagnostics. The
following error codes are possible:
Code (hex)
Error
8001
Overrange
8002
Open circuit
8004
Measured value invalid/no valid measured value available
8010
Configuration invalid
8040
Module defective
8080
Below range