Startup and validation
105739_en_04
PHOENIX CONTACT
47
7
Startup and validation
7.1
Initial startup
Table 7-1
Steps for startup
Step
Relevant section and literature
Set the address.
see Section 4.1.3 “Setting the DIP switch” on page 28
Install the module in the Axioline F station.
“Assembly, removal, and electrical installation” on page 27
UM EN AXL F SYS INST user manual
Connect the bus system and supply voltage cables to the
Axioline F station.
UM EN AXL F SYS INST user manual or documentation for
the bus coupler
Wire the inputs according to your application.
see Section 6 “Connection examples for safe outputs” on
Before applying the operating voltage:
–
Make sure that there are no wiring errors (e.g., cross-
circuit or short circuit) or grounding errors by testing with
a multimeter.
–
Make sure that functional earth ground is connected.
Connect the necessary voltages to the Axioline F station.
UM EN AXL SYS INST user manual or documentation for
the module
Connect the necessary voltages (U
O
) to the module.
Once the operating voltage has been applied:
–
If possible, measure the waveform of the voltages to
make sure that there are no deviations.
–
Measure the input voltages on the module to make sure
that they are in the permissible range.
–
Use the LEDs on the module to check that the module
starts up without any errors.
Check the assembly and installation.
Checklist see Section 4 “Assembly, removal, and electrical
Carry out the necessary parameterization.
see Section 5 “Parameterization of the module” on page 33
Documentation for the PROFIsafe controller
Program the safety function.
User manuals for the function blocks used
Documentation for the PROFIsafe controller
Perform a function test and validation. Check whether the
safety function responds as planned during programming
and parameterization.
Checklist “Validation” on page 83
When connecting the supply voltages, use the diagnostics
and status indicators to check whether the module has
started up correctly or whether any errors are indicated.
Instructions on how to proceed in the event of an error: see
Summary of Contents for Axioline F
Page 1: ...User manual Axioline F safety module with safe digital outputs UM EN AXL F PSDO8 3 1F ...
Page 8: ...AXL F PSDO8 3 1F 8 PHOENIX CONTACT 105739_en_04 ...
Page 22: ...AXL F PSDO8 3 1F 22 PHOENIX CONTACT 105739_en_04 ...
Page 32: ...AXL F PSDO8 3 1F 32 PHOENIX CONTACT 105739_en_04 ...
Page 36: ...AXL F PSDO8 3 1F 36 PHOENIX CONTACT 105739_en_04 ...
Page 46: ...AXL F PSDO8 3 1F 46 PHOENIX CONTACT 105739_en_04 ...
Page 50: ...AXL F PSDO8 3 1F 50 PHOENIX CONTACT 105739_en_04 ...
Page 62: ...AXL F PSDO8 3 1F 62 PHOENIX CONTACT 105739_en_04 ...
Page 64: ...AXL F PSDO8 3 1F 64 PHOENIX CONTACT 105739_en_04 ...
Page 84: ...AXL F PSDO8 3 1F 84 PHOENIX CONTACT 105739_en_04 ...
Page 86: ...AXL F PSDO8 3 1F 86 PHOENIX CONTACT 105739_en_04 ...