Parameterization of the module
105739_en_04
PHOENIX CONTACT
33
5
Parameterization of the module
5.1
Setting the F-Parameters and i-Parameters
Parameterization includes the following:
–
Assigning the PROFIsafe address
–
Parameterizing outputs
PROFIsafe address
The PROFIsafe address is a unique ID for the module in the PROFIsafe network topology.
It is assigned in the configuration software.
•
Set the address that you assigned earlier in the configuration software using the DIP
switch on the module: see Section 4.1.3 “Setting the DIP switch” on page 28.
Parameterization of
outputs
The parameterization of the safe outputs determines the behavior of the module and
influences the safety integrity that can be achieved.
The controller automatically writes the parameterization created in the parameterization tool
to the module on every power up or reset.
The following conditions must be met:
–
Supply voltage is present
–
Local bus is in the RUN state
–
Communication connection has been established between the controller and the
module
The module cannot be operated if it is not parameterized. The FS LED flashes.
The module is ready to operate if the parameters for all outputs are valid and transmitted
without errors. Valid output data is only written in this state. In any other state, every output
is set to the safe state.
If errors are detected during parameterization, the parameterization data is not applied. The
FS LED flashes to indicate that the parameterization is invalid.
In addition, the error is indicated at the controller. In this case, check and correct the
settings. Information on error messages and troubleshooting: see Section 8 “Errors:
messages and removal” on page 51.
F-Parameters and
i-Parameters
Assign the parameterizable F-Parameters and i-Parameters. Overview of the module
parameters and possible settings: Section “Appendix: F-Parameters and i-Parameters” on
The communication address configured in the controller project must match the address
set on the device.
The settings on the device take effect after a power up.
Summary of Contents for Axioline F
Page 1: ...User manual Axioline F safety module with safe digital outputs UM EN AXL F PSDO8 3 1F ...
Page 8: ...AXL F PSDO8 3 1F 8 PHOENIX CONTACT 105739_en_04 ...
Page 22: ...AXL F PSDO8 3 1F 22 PHOENIX CONTACT 105739_en_04 ...
Page 32: ...AXL F PSDO8 3 1F 32 PHOENIX CONTACT 105739_en_04 ...
Page 36: ...AXL F PSDO8 3 1F 36 PHOENIX CONTACT 105739_en_04 ...
Page 46: ...AXL F PSDO8 3 1F 46 PHOENIX CONTACT 105739_en_04 ...
Page 50: ...AXL F PSDO8 3 1F 50 PHOENIX CONTACT 105739_en_04 ...
Page 62: ...AXL F PSDO8 3 1F 62 PHOENIX CONTACT 105739_en_04 ...
Page 64: ...AXL F PSDO8 3 1F 64 PHOENIX CONTACT 105739_en_04 ...
Page 84: ...AXL F PSDO8 3 1F 84 PHOENIX CONTACT 105739_en_04 ...
Page 86: ...AXL F PSDO8 3 1F 86 PHOENIX CONTACT 105739_en_04 ...